8.2 Replace the Fuse
Danger to life due to high voltage
Prior to performing any work on the product, always disconnect it from
all sources and wait for 2 minutes at least.
Hot surface
The unit may be hot during operation. Before touching the unit,
shutdown and wait for 20minutes.
1.
Turn the unit off and disconnect all connections: AC, PV, attached load, and external battery
connections; wait for at least 2 minutes for any internal charge to dissipate.
2.
Pull out the fuse holder underneath the AC/Grid socket.
3.
Replace the broken fuse with new one. Note the rating must be 6.3A/250V
4.
P Place the fuse assembly back into the AC/Grid socket.
.
Fig. 8-2 Grid O/P fuse replacement
WARNING
!
CAUTION
!
User Manual
22 Hybrid CPSHB300ETR-IN