5
Installation
5.1 Safety Instruction
Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires.
Do not install the unit on easily flammable materials and where
flammable materials are stored.
Carefully remove the unit from its packaging and inspect for external damage. If you find any
imperfections, please contact your local dealer.
The PV input interface can only be connected with PV panel(s), ant the external battery connector can
only accept SLA battery types in 24VDC configuration.
Disconnect whole connections before servicing.
Do not connect this unit to an AC source or generator.
When a photovoltaic panel is exposed to light, it generates a DC voltage. When connected to this
equipment, a photovoltaic panel will charge the DC link capacitors.
Energy stored in this equipment’s DC link capacitors presents a risk of electric shock. Even after the unit
is disconnected from the grid, external battery and photovoltaic panels, high voltages may still exist
inside the unit. Do not remove the casing until at least 2 minutes after disconnecting all power sources.
Although designed to meet all safety requirements, some parts and surfaces of unit are still hot during
operation. To reduce the risk of injury, do not touch the surfaces of unit during operation.
5.2 Selecting the Installation Location
The points below help you select a suitable installation location, thus avoiding any potential damages to
both device and operators:
1)
Obviously the location selected must be suitable for the units’ dimensions, with room to spare.
2)
Do not install the unit on structures constructed of flammable or thermo labile materials.
3)
Never install the unit in environment of little or no air flow, nor dust environment.
4)
The unit must be installed indoors.
5)
Do not expose the unit to direct sunlight, in order to avoid the power and efficiency de-rating
caused by excessive heating.
6)
The humidity of the installation location should be 0~95% without condensation.
7)
The ambient temperature of the unit should be -10
℃
~+50
℃
.
8)
The installation location must be freely and safely to get at all times.
9)
Vertically installation only. Never install in horizontal positions, and avoid forward and sideways
tilting; (
observe drawings below
)
WARNING
!