5.4.4 Grounding
AC Grounding
The CPS Mini Central inverter must be connected to the AC grounding conductor of the power distribution grid via
the ground terminal (PE).
PV Grounding
The grounding conductor in the framework of the PV array must be connected to the PV grounding conductor and
the DC grounding conductor. The cross-section of the grounding conductor corresponds to the cross-section of the
largest conductor in the DC system.
DC Grounding Conductor
A DC grounding conductor may be required by the Authority Having Jurisdiction (AHJ). Use the terminal block for
the PV grounding conductor and DC grounding conductor.
Ground kit
If PV modules of the PV system require POSITIVE or NEGATIVE to connect to GROUND, the output of inverter
should connect to grid with an isolating transformer. The connection method is below:
N of transformer should not be connected to PE.