INPUT/OUTPUT CONFIGURATION CONT.
Step 3: Input configuration
Insert the input cable through the appropriate cable gland (not included) and connect the three wires to
the input terminal block.
BACKFEED PROTECTION OPERATION
1. If the Bypass circuit is shorted and the UPS is running in Line Mode or Battery Mode, backfeed
protection will be active and the external isolation device (Magnetic Contactor) will open.
2. Save your data and perform a controlled shutdown.
3. Contact CyberPower for repair.
1
2
3
Step 4: Output configuration
Insert the output cable through the appropriate cable gland (not included) and connect the three wires to
the output terminal block.
Step 5: Fix the terminal block cover on the Maintenance Bypass Module
Tighten the four screws to fix the terminal block cover on the Maintenance Bypass Module. Replace the
inspection window cover using four screws.
4
5
MAINTENANCE BYPASS MODULE
INSTALLATION CONT.
Warning!
A CyberPower Step-Down Transformer is required for supplying 120V output to connected equipment. To
prevent damage to connected equipment, do not attempt to separate the output voltage, from the hardwire
block or outlets, into two 120V outputs on this UPS. If you attempt to supply two separate 120V outputs to
your equipment, that equipment can be damaged when the UPS switches to battery mode.
L1
L2
L1
L2
AC INPUT
AC OUTPUT