28
Short circuit clearance
enabled/disabled
disabled
Power strategy**
normal/ECO/converter
normal
Rated output voltage
208/220/230/240V
230V
Output frequency
50/60Hz
50Hz
Bypass voltage low range
10%,15%,20%
15%
Bypass voltage high range
10%,15%
10%
Bypass frequency range
1%~10%
10%
ECO voltage range
10%,15%
10%
ECO frequency range
1%~10%
5%
Ext. Bat Type***
Standard/Customized
Standard
Ext. Bat Pack ****
1Packs~15Packs
0 Packs
Automatic battery tests period
0~45days
7days
Set running time
Day: hour: minute: second
0000:0000:00~9999:23:59:59
Running time
Restore default setting
Yes/NO
*Password is AAAA when enabled.
**Read the chapter of 8.1 and 8.2, before using ECO or converter function. UPS
need shut down, if change work mode from converter to others.
***Large current Charging when Ext. Bat Type is "Customized".
****Small current Charging when
Ext. Bat Pack≤1 Packs. Large current Charging
when Ext. Bat Pack >1 Packs.