24
•
Enable Low Current Alerts
•
Low Current (Amps)
•
Low Grace Period (ms)
•
Enable Cyber Breaker® Virtual Circuit Breaker™
•
Enable High Current Alerts
•
High Current (Amps)
•
High Grace Period (ms)
•
Reboot delay (sec.)
•
Reboot off (sec.)
Note:
The
Enable Low/High Current Alerts
options must be selected for
the Low/High Current and Low/High Grace Period settings to be
operational. See
Setting High/Low Currents and Grace Periods
. Click in
the checkbox of an option to activate it.
1. To change the label for an outlet, click in the box next to
Outlet Label
and enter a new name using a maximum 15 characters.
2. To change the Reboot delay/off times, click in the box next to either
option and enter a new number between 0 and 6000.
3. Click
Save Properties
when done.
Setting High/Low Currents and Grace Periods
When the current rises above or falls below the set current level threshold for
longer than the set grace period, current alerts trigger syslogs or SNMP traps.
Do the following to enable high/low current alerts, grace periods and the Virtual
Circuit Breaker ™. Once enabled, a log and an SNMP trap will be sent if the
measured current drops below or rises above the limit for longer than the low or
high grace period.
1. To enable low current alerts, click in the box next to
Enable Low
Current Alerts
. A checkmark appears indicating the option is active.
Click again to remove the checkmark
and disable the option.
2. To change the Low Current or Low Grace period times, click in the box
next to either option and enter a new time.
3. To enable high current alerts, click in the box next to
Enable High
Current Alerts
. A checkmark appears indicating the option is active.
Click again to remove the checkmark
and disable the option.