Advanced Energy-Saving Patented Bypass Technology
CyberPower’s patented GreenPower UPS™ with Bypass Technology reduces UPS energy
costs by up to 75% compared to conventional UPS models. Even when utility power is
normal, conventional UPS models constantly pass power through a transformer. By contrast,
under normal conditions the advanced circuitry of a GreenPower UPS™ bypasses the trans-
former. As a result, the power efficiency is significantly increased while decreasing waste
heat, using less energy, and reducing energy costs.
When an abnormal power condition occurs, the GreenPower UPS™ automatically runs
power through its transformer to regulate voltage and provide “safe” power. Since utility
power is normal over 88% of the time, the GreenPower UPS™ operates primarily in its
efficient bypass mode.
The GreenPower UPS™ is also manufactured in accordance with the Restriction on Hazardous Substances
(RoHS) directive making it one of the most environmentally-friendly on the market today.
CYBERPOWER GREENPOWER UPS™ TECHNOLOGY
G
REEN
P
OWER
UPS
™
Energy-Saving Technology
Please visit www.CyberPowerSystems.com for a copy of the Limited Warranty and Connected
Equipment Guarantee.
Where Can I Get More Information?
The application of the United Nations Convention of Contracts for the International Sale of
Goods is expressly excluded. CyberPower is the warrantor under this Limited Warranty.
For further information please feel free to contact CyberPower at:
Cyber Power Systems (USA), Inc. 4241 12th Ave E., STE 400, Shakopee, MN 55379;
call us at
(877) 297-6937
; or submit a web ticket online at
cyberpowersystems.com/support
.
Cyber Power Systems (USA), Inc. encourages environmentally sound methods for disposal and
recycling of its UPS products. Please dispose and/or recycle your UPS and batteries in accordance
to the local regulations of your state.
This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device
may not cause harmful interference, and (2) this device must accept any interference received, including interference
that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the
FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the
following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment to an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
Warning: Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority
to operate the equipment.
Canadian Compliance Statement
CAN ICES-3 (B)/NMB-3(B)
LIMITED WARRANTY AND CONNECTED EQUIPMENT GUARANTEE
FCC COMPLIANCE STATEMENT
WARNING: This product can expose you to chemicals including bisphenol A (BPA) and styrene, which is known to the State of
California to cause reproductive harm and cancer. For more information, go to www.P65Warnings.ca.gov.
© 2022 CyberPower Systems (USA), Inc. PowerPanel® Personal is a trademark of Cyber Power Systems(USA) Inc.
All rights reserved. All other trademarks are the property of their respective owners.
TECHNICAL SPECIFICATIONS
SYSTEM FUNCTION BLOCK DIAGRAM
Input
Output
Battery Mode
Normal Mode
EMI
Filter
Surge
Suppressor
Inverter
Charger
AC / DC
Battery
AVR
Model
BL1450U
Capacity
1,450VA / 810W
Nominal Input Voltage
120V
Input Frequency
60 Hz ± 3 Hz
On-Battery Output Voltage
120Vac ± 5%
Max. Load for UPS Outlets (5 Outlets)
1,450VA / 810W
Max. Load for Full-Time Surge Protection outlets
(10 Outlets)
12 A
On-Battery Output Wave Form
Simulated Sine Wave
Operating Temperature
+ 32°F to 104° F / 0° C to 40° C
Operating Relative Humidity
0 to 90% non-condensing
Size (W x H x D)
3.9" x 9.8" x 13.7" (99 x 249 x 348 mm)
Net Weight
22.2 lbs / 10.1 kg
Battery Type
CyberPower / RB1270X2C
Typical Battery Recharge Time
8 hours to 90% capacity from total discharge
Typical Battery Life
3 to 6 years, depending on number of discharge/
recharge cycles
Recommended Battery
Sealed Maintenance Free Lead Acid Battery
Safety Approvals
UL1778(UPS), CSA C22.2 No. 107, FCC/DoC Class B