background image

 

1. Input Connector 

Use this input connector to daisy chain the next Battery module. Remove the connector cover for   
access. 

 

2. On-board Replaceable Fuse Cover 

Replaceable fuse is accessible from the rear panel. It must be done by qualified personnel. 

 

3. Battery Output Connector 

Use this output Connector to connect the Battery module to the Power module or to the next 
Battery module.

 

 

CONNECTION #1 : POWER MODULE(UPS) WITH ONE BATTERY MODULE 

 

Step 1:Loosen  the  two  screws  to  remove  the  battery  cable  retention  bracket  of  the  Power 

module. 

Step 2:Use the battery cable of the Battery module to connect the Battery module to the Power 

module. 

Step 3: Rotate the battery cable retention bracket and tighten the two screws to fix battery cable.

 

 

     

 

 

 

 

 

 

CONNECTION #2 : POWER MODULE(UPS) WITH MULTIPLE BATTERY 
MODULES 

 
Step 1:Connect the 1

st

 Battery module to the Power module using battery cable. (Refer to above 

steps of connection #1) 

Step 2:Loosen  the  two  screws  to  remove  the  battery  cable  retention  bracket  of  the  1

st

  battery 

module. 

Step 3: Use the battery cable to connect the 2

nd

 Battery module to the 1

st

 Battery module. 

Step 4: Rotate the battery cable retention bracket and tighten the two screws to fix battery cable.

 

 

 

 

 

 

 

 

TECHNICAL SPECIFICATIONS 

 

Model 

 

BPSE36V45A 

BPSE72V45A 

Battery 

Sealed Maintenance Free 
Lead Acid Battery 

12V / 7Ah x3pcs x2sets 

12V / 7Ah x6pcs x2sets 

Rated Battery Voltage 

36Vdc 

72Vdc 

Overload Protection 

Fuse 

Physical 

 

Maximum Dimensions 
(HxWxD) (mm) 

225 x 151 x 394 

337 x 196 x416 

Weight (kg) 

17.2 

34.2   

Environment 

 

Operating Temperature 

0

C to 40

Relative Humidity 

0 to 90% (Non-condensing) 

 

For more information, visit 

www.cyberpower.com

   

All rights reserved. Reproduction without permission is prohibited. 

 

 

 