background image

 

 

 
 
 

CAUTION! 

Read and follow the 

IMPORTANT SAFETY INSTRUCTIONS 

before servicing the battery. 

Service the battery under the supervision of personnel knowledgeable of

 

batteries and their 

precautions.

 

CAUTION! 

Use only the specified type of battery. See your dealer for replacement batteries. 

CAUTION! 

The battery may present the risk of electrical shock. Do not dispose of batteries in a fire, as they 

may explode. Follow all local ordinances regarding proper disposal of batteries. 

CAUTION! 

Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes and 

may be toxic. 

CAUTION! 

A battery can present a high risk of short circuit current and electrical shock. Take the following 

precautions before replacing the battery: 
1. Remove all watches, rings or other metal objects. 
2. Only use tools with insulated handles. 
3. 

DO NOT 

lay tools or other metal parts on top of battery or any battery terminals. 

4. Wear rubber gloves and boots. 
5. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of ground. 

CONTACT WITH A GROUNDED BATTERY CAN RESULT IN ELECTRICAL

 

SHOCK! 

The likelihood of 

such shock will be reduced if such grounds are removed during installation and maintenance (applicable to a 
UPS and a remote battery supply not having a grounded circuit) 

 

BATTERY REPLACEMENT PROCEDURE 

 
1. Turn off and unplug all connected equipment. 
2. Turn the UPS off and unplug it from the AC power source. 
3. Turn the UPS on its side. 
4. Remove the retaining screw located on the bottom of the UPS. 
5. Slide the battery compartment cover completely off of the unit. 
6. Remove the batteries from the compartment. 
7. Disconnect the battery wires from the batteries. 
8. Install the replacement batteries by connecting the red wire (+) and black wire (-) to the same color 

connectors from the battery pack. 

9. Put the batteries back into the compartment. 
10. Slide back the battery compartment cover and tighten the retaining screw. 
11. Recharge the UPS for 8-16 hours to fully charge the battery. 
 
BR700ELCD/ BR1000ELCD 
 

 
 
 
 
 
 
 

BR1200ELCD 
 

 

 

 
 

LCD Indication 

 
 
 
 
 

Line Mode 

 

Display SW 

Press 

UPS Status Display 

Capacity Display 

Digital Value Display 

 

 

 

 

Load 

Cap. 

Battery 

Cap.

 

Input 

Voltage 

Output 

Voltage 

Run 

Time 

of 

Load 

of Batt.

Initial 

V X -- X  V  X 

 

 

 

 

1st  V 

-- 

V X    V    

2nd 

V X -- X  V  X 

 

 

 

 

3rd 

V X -- X  X  V 

 

 

 

 

4th 

V X -- X  V  X  V 

 

 

 

 

5th(Return)  V X -- X  V  X 

 

 

 

 

Press >3sec 

(Sound Disable) 

X -- -- -- -- -- -- -- 

Press >3sec 

again 

(Sound Enable) 

X -- -- -- -- -- -- -- 

(Overload) V 

-- 

V -- -- -- -- --

--

--

“V” : Illuminated,    “X” : Not Illuminated,    “--“ : Either

 

 
Battery Mode 

 

Display SW 

Press 

UPS Status Display 

Capacity Display 

Digital Value Display 

 

 

 

 

Load 

Cap. 

Battery 

Cap.

 

Input 

Voltage 

Output 

Voltage 

Run 

Time 

of 

Load 

of Batt.

Initial 

X V -- X  X  V 

 

 

 

 

1st  X 

-- 

X V    V    

2nd 

X V -- X  V  X 

 

 

 

 

3rd 

X V -- X  X  V 

 

 

 

 

4th 

X V -- X  X  V  V 

 

 

 

 

5th(Return)  X V -- X  X  V 

 

 

 

 

Press >3sec 

(Sound Disable) 

X -- -- -- -- -- -- -- 

Press >3sec 

again 

(Sound Enable) 

X -- -- -- -- -- -- -- 

(Overload) X 

-- 

V -- -- -- -- --

--

--

“V” : Illuminated,    “X” : Not Illuminated,    “--“ : Either

 

 
 
 

 
 
 

 
CyberPower’s Green Commitment

 

CyberPower is dedicated to the development of green products, and has adopted   
Green practices throughout its business, including: membership in Climate Savers   
Computing Initiative (CSCI), accordance with the Restriction on Hazardous   
Substances (RoHS), Waste Electrical and Electronic Equipment (WEEE) protocols,   
as well as ISO 14001 and IECQ QC080000. CyberPower pledges to provide the   
advanced energy solution for the environment and become a leading eco-friendly   
organization in the UPS industry. 

 

Reduce Energy Cost with GreenPower UPS

TM

 Technology 

CyberPower’s goal is not only to provide eco-friendly products but also to bring the best value for consumers.

 

The advanced energy-saving design improves the operating efficiency and eliminates waste energy 
consumption

.

 As a result, consumers will enjoy significant energy cost savings with the adoption of

 

GreenPower UPS

TM

 

technology. 

 

 
 

 

Problem

 

Possible Cause 

Solution

 

Full-time surge protection 

outlets stop providing power 

to equipment. Circuit 

breaker button is projecting 

from the side of the unit.

Circuit breaker has 

tripped due to an 

overload. 

Turn the UPS off and unplug at least one 

piece of equipment. Wait 10 seconds, reset 

the circuit breaker by depressing the button, 

and then turn the UPS on.

 

The UPS does not perform 

expected runtime. 

Battery not fully 

charged. 

Recharge the battery by leaving the UPS 

plugged in. 

Battery is slightly worn 

out. 

Contact CyberPower Systems about 

replacement batteries.

The UPS will not turn on. 

The on/off switch is 

designed to prevent 

damage by rapidly 

turning it off and on.

Turn the UPS off.    Wait 10 seconds and then 

turn the UPS on. 

The battery is worn out.

Contact CyberPower Systems about 

replacement batteries

Mechanical problem. 

Contact CyberPower Systems at 

www.cyberpower.com

 

PowerPanel® Personal 

Edition is inactive. 

The USB cable is not 

connected. 

Connect the USB cable to the UPS unit and 

an open serial port on the back of the 

computer. You must use the cable that came 

with the unit.

 

The unit is not providing

battery power. 

Shutdown your computer and turn the 

UPS off. Wait 10 seconds and turn the 

UPS back on. This should reset the unit. 

 

Additional troubleshooting information can be found at 

www.cyberpower.com

 

For more information, Visit 

www.cyberpower.com

 or contact 

CyberPower Systems B.V. 

All rights reserved. Reproduction without permission is prohibited. 

6F, No. 32, Sec. 1, Chenggong Rd., Nangang District, Taipei 115, Taiwan 

 

 

 

TROUBLESHOOTING 

DEFINITIONS FOR ILLUMINATED LCD INDICATORS 

 

CYBERPOWER GREENPOWER UPS™ TECHNOLOGY 

BATTERY REPLACEMENT 

Reviews: