background image

 

TROUBLESHOOTING 

Problem Possible 

Cause 

Solution 

Full-time surge protection 

outlets stop providing 

power to equipment. 

Circuit breaker has tripped 

due to an overload. 

Turn the UPS off and unplug at least one piece of equipment.  

Wait 10 seconds, reset the circuit breaker by depressing the 

button, and then turn the UPS on. 

Battery not fully charged. 

Recharge the battery by leaving the UPS plugged in. 

The UPS does not perform 

expected runtime. 

Battery is slightly worn out. 

Contact CyberPower Systems about replacement batteries at 

tech@cyberpowersystems.com 

The on/off switch is 

designed to prevent 

damage by rapidly turning 

it off and on. 

Turn the UPS off.  Wait 10 seconds and then turn the UPS on. 

 

The unit is not connected 

to an AC outlet. 

The unit must be connected to a 110/120v 60Hz outlet. 

The battery is worn out. 

Contact CyberPower Systems about replacement batteries at 

tech@cyberpowersystems.com 

 

 

The UPS will not turn on. 

Mechanical problem. 

Contact CyberPower Systems about at 

tech@cyberpowersystems.com 

The serial cable is not 

connected. 

Connect the serial cable to the UPS unit and an open serial port 

on the back of the computer.  You must use the cable that came 

with the unit. 

The serial cable is 

connected to the wrong 

port. 

Check the back of the computer for an additional serial port.  

Move the cable to this port. 

The unit is not  

providing battery power. 

Shutdown your computer and turn the UPS off.  Wait 10 

seconds and turn the UPS back on.  This should reset the unit. 

 

 

 

 

 

PowerPanel™ Plus is 

inactive (all icons are gray). 

The serial cable is not the 

cable that was provided 

with the unit. 

You must use the cable that was included with the unit for the 

software and the unit to be able to communicate. 

 

 

SPECIFICATIONS 

Model CPS825AVR 

General 

Capacity 

825VA (410W) 

Frequency 57Hz 

to 

63Hz 

Input 

Voltage Range 

92v – 145v 

AVR Max. boost 13% of input voltage for output regulation while 

input voltage is from 8% to 30% under nominal. 

Line Conditioning Regulation 

AVR buck 13% of input voltage for output regulation while input 

voltage is from 8% to 26% over nominal 

On Battery Output Voltage 

Regulation 

120 Vac ±5% (user adjustable) 

Transfer Time 

4ms typical, including detection time 

On Battery Output Wave Form 

Simulated Sine Wave Form 

UPS-Output 

Max. Load 

825VA (410W) 

Full-time Surge Protection 

Output 

Max. Load 

12 Amps 

Battery Type 

Sealed, Maintenance-free lead acid battery 

Number of Batteries 

12V / 9AH x 1 

Battery 

Recharge Time 

4 to 8 hours from total discharge 

Communication 

RS-232 with Plug and Play interface / USB Adapter 

Win 98, Win NT, Win 2000, Win ME, Win XP 

LED Indicators 

Power On, Electrical Wiring Fault 

3 Battery-powered and full-time surge protection 

Interface 

Output Receptacles 

6 full-time surge protection 

 

Summary of Contents for CPS825AVR

Page 1: ...User Manual for CPS825AVR with USB Interface and PowerPanel Plus Software ADDITIONAL INSTALLATION TIPS CAN BE FOUND AT www cyberpowersystems com faqs htm...

Page 2: ...source before servicing the battery or installing a computer component DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT CyberPower Systems does not sell products for life support or medical applicatio...

Page 3: ...ard 1 UPS unit DESCRIPTION 5 Power Switch Can be used as the master on off switch for computer equipment connected to the battery power supplied outlets 6 Power On Indicator This LED is illuminated wh...

Page 4: ...ephone icon can be used to protect a telephone or fax machine line 5 Plug the UPS into a properly grounded wall outlet Make sure the wall outlet is protected by a fuse or circuit breaker and does not...

Page 5: ...e will appear on your screen for a few seconds and then minimize It will appear as a blue and white battery icon located in the system tray near the clock FOR WINDOWS NT 1 Click on Start point to Sett...

Page 6: ...o an AC outlet turn the UPS on and then start your computer 8 Windows will find New Hardware 9 Insert the PowerPanel Plus primary disk into the floppy drive 10 Follow the on screen instructions 11 Onc...

Page 7: ...n your computer system on It can only be set when a Scheduled Off is also set Scheduled On settings that are set to occur within seven days will be displayed When the UPS is in standby after the Sched...

Page 8: ...ault Click this button to return the software to original factory settings 9 Cancel This button exits the window without saving changes 10 OK This button exits the window and saves changes 11 UPS Comm...

Page 9: ...will display the names and location of any files that were auto saved by the software TESTING YOUR UPS SYSTEM Once you have set up your UPS system you may wish to test it Make sure that the UPS has b...

Page 10: ...armful to skin and eyes and may be toxic CAUTION A battery can present a high risk of short circuit current and electrical shock Take the following precautions before replacing the battery 1 Remove al...

Page 11: ...REMINDER Batteries are consider HAZARDOUS WASTE and must be disposed properly Contact your local government for more information about proper disposal and recycling of batteries...

Page 12: ...Beep Overload Occurs in the Battery power Supplied Outlets Turn the UPS off and unplug at least one piece of equipment from the UPS Wait 5 seconds reset the circuit breaker and turn the UPS on Off Off...

Page 13: ...the computer for an additional serial port Move the cable to this port The unit is not providing battery power Shutdown your computer and turn the UPS off Wait 10 seconds and turn the UPS back on This...

Page 14: ...erage under the Limited Warranty and the Power Control Guarantee Registration is not required for Limited Warranty coverage but note if you do not complete a registration card you will be required to...

Page 15: ...mple a sales receipt that establishes you as the Initial Customer the original consumer purchaser of the Product within ten 10 days of the event for which you want to make a claim for warranty service...

Page 16: ...volt power lines in the United States and Canada transients surges or spikes on standard telephone land lines PBX telephone equipment lines or Base 10 100T Ethernet lines when properly installed and c...

Page 17: ...pment into an outlet on a circuit different from that to which the receiver is connected 4 Consult the dealer or an experienced radio TV technician for help Any special accessories needed for complian...

Reviews: