Chapter 2 Installation Instruction
20
HSTP3T 60-500 KE User Manual
Note
The recommended cable section for power cables are only for situations described below
:
Ambient temperature
:
30
℃
.
AC loss less than 3%
,
DC loss less than 1%
,
The length of the AC power cables are no
longer than 50 m and the length of the DC power cables are no longer than 30 m.
Currents listed in the table are based on the 380V system (Line-to-line voltage).
The size of neutral lines should be 1.5~1.7 times the value listed above when the
predominant load is non-linear.
2.6.2 Specifications for Power Cables Terminal
Specifications for power cables connector are listed as Table 2.3.
Table 2.3 Requirements for power module terminal
Type
Port
Connection
Bolt
Torque Moment
60kVA
Mains input
Cables crimped OT terminal
M6
4.9Nm
Bypass Input
Cables crimped OT terminal
M6
4.9Nm
Battery Input
Cables crimped OT terminal
M6
4.9Nm
Output
Cables crimped OT terminal
M6
4.9Nm
PE
Cables crimped OT terminal
M6
4.9Nm
90kVA
120kVA
Mains input
Cables crimped OT terminal
M6
4.9Nm
Bypass Input
Cables crimped OT terminal
M6
4.9Nm
Battery Input
Cables crimped OT terminal
M6
4.9Nm
Output
Cables crimped OT terminal
M6
4.9Nm
PE
Cables crimped OT terminal
M6
4.9Nm
80kVA
100kVA
Mains input
Cables crimped OT terminal
M6
4.9Nm
Bypass Input
Cables crimped OT terminal
M6
4.9Nm
Battery Input
Cables crimped OT terminal
M8
13Nm
Output
Cables crimped OT terminal
M6
4.9Nm
PE
Cables crimped OT terminal
M6
4.9Nm
150kVA
200kVA
Mains input
Cables crimped OT terminal
M10
15Nm
Bypass Input
Cables crimped OT terminal
M10
15Nm
Battery Input
Cables crimped OT terminal
M10
15Nm
Output
Cables crimped OT terminal
M10
15Nm
PE
Cables crimped OT terminal
M10
15Nm
250kVA
300kVA
Mains input
Cables crimped OT terminal
M12
28Nm
Bypass Input
Cables crimped OT terminal
M12
28Nm
Battery Input
Cables crimped OT terminal
M12
28Nm
Output
Cables crimped OT terminal
M12
28Nm
PE
Cables crimped OT terminal
M12
28Nm
400kVA
500kVA
Mains input
Cables crimped OT terminal
M16
96Nm
Bypass Input
Cables crimped OT terminal
M16
96Nm
Battery Input
Cables crimped OT terminal
M16
96Nm
Output
Cables crimped OT terminal
M16
96Nm
PE
Cables crimped OT terminal
M16
96Nm