23
HSTP3T 60-500 KE User Manual
Chapter 2 Installation Instruction
3. Connect the protective earth wire to protective earth terminal (PE).
4. Connect the AC input supply cables to the Input terminal and AC output supply cables to
the Output terminal.
5. Connect the Battery cables to the Battery terminal.
6. Check to make sure there is no mistake and re-install all the protective covers.
Attention
The operations described in this section must be performed by authorized electricians or
qualified technical personnel. If you have any difficulties, contact the manufacturer or agency.
Warning
Tighten the connections terminals to enough torque moment, refer to Table 2.3, and
please ensure correct phase rotation.
The grounding cable and neutral cable must be connected in accordance with local and
national codes.
Load must be connected to the same ground as that of UPS system.
2.7 Control and Communication Cables
The front panel of the bypass module provides dry contact interface (J2-J11) and
communication interface (RS232, RS485, SNMP, Intelligent card interface and USB port)
,
as it
is shown in Fig.2-13.
Fig.2-13-1 Dry contact &communication interface of 60kVA-300kVA