background image

   

 

 

 

 

 

 

 

 

 

 

 

User’s Manual 

 

HSTP3T15KE-C / KEBC-C 

HSTP3T20KE-C / KEBC-C 

 

 

 

 

 

 

 

 

 

CyberPower Systems, Inc. 

www.cyberpower.com 

Библиотека СОК  

Summary of Contents for HSTP3T15KE-C

Page 1: ...User s Manual HSTP3T15KE C KEBC C HSTP3T20KE C KEBC C CyberPower Systems Inc www cyberpower com Библиотека СОК ...

Page 2: ...Ver 1 0 0 ...

Page 3: ...iliar with the operation debug and maintenance of the equipment Warning Label The warning label indicates the possibility of human injury or equipment damage and advises the proper step to avoid the danger In this manual there are three types of warning labels as below Labels Description Danger Serious human injury or even death may be caused if this requirement is ignored Warning Human injury or ...

Page 4: ... 10 minutes for internal discharge Use a multi meter to measure the voltage on terminals and ensure the voltage is lower than 36V before operation Attention The earth leakage current of load will be carried by RCCB or RCD Initial check and inspection should be performed after long time storing of UPS Maintenance Replacement Danger All the equipment maintenance and servicing procedures involving in...

Page 5: ...osion or poor performance When connecting the battery follow the precautions for high voltage operation before accepting and using the battery check the appearance the battery If the package is damaged or the battery terminal is dirty corroded or rusted or the shell is broken deformed or has leakage replace it with new product Otherwise battery capacity reduction electric leakage or fire may be ca...

Page 6: ...out of control swell or leak Be sure to replace the battery before these phenomena happen If a battery leaks electrolyte or is otherwise physically damaged it must be replaced stored in a container resistant to sulfuric acid and disposed of in accordance with local regulations If electrolyte comes into contact with the skin the affected area should be washed immediately with water Disposal Warning...

Page 7: ... 2 5 Cable Entry 11 2 6 Power Cables 12 2 6 1 Specifications 12 2 6 2 Specifications for Power Cables Terminal 12 2 6 3 Circuit Breaker 13 2 6 4 Connecting Power Cables 13 2 7 Control and Communication Cables 14 2 7 1 Dry Contact Interface 14 2 7 2 Communication Interface 19 2 7 3 Communication Setting 19 Chapter 3 LCD Panel 21 3 1 Introduction 21 3 2 LCD panel for Cabinet 21 3 2 1 LED Indicator 2...

Page 8: ... Instruction for Maintaining UPS 39 5 3 Instruction for Maintaining Battery string 39 5 3 1 Installation of internal battery 40 Chapter 6 Product Specification 42 6 1 Applicable Standards 42 6 2 Environmental Characteristics 42 6 3 Mechanical Characteristic 42 6 4 Electrical Characteristics 43 6 4 1 Electrical Characteristics Input Rectifier 43 6 4 2 Electrical Characteristics Intermediate DC Link...

Page 9: ...g 1 1 Fig 1 1 UPS Configuration 1 2 Operation Mode The Tower UPS is an on line double conversion UPS that permits operation in the following modes Normal mode Battery mode Bypass mode Maintenance mode manual bypass ECO mode Auto restart mode Frequency Converter mode 1 2 1 Normal Mode The inverter of power modules continuously supply the critical AC load The rectifier charger derives power from the...

Page 10: ... a transfer of the load from the inverter to the bypass source with no interruption in power to the critical AC load Should the inverter be asynchronous with the bypass the static switch will perform a transfer of the load from the inverter to the bypass with power interruption to the load This is to avoid large cross currents due to the paralleling of unsynchronized AC sources This interruption i...

Page 11: ...o Battery Mode and the inverter provide powers to the loads Fig 1 6 ECO Mode operation diagram Note There is a short interruption time less than 10ms when transfer from ECO mode to battery mode it must be sure that the interruption has no effect on loads 1 2 6 Auto restart Mode The battery may become exhausted following an extended AC mains failure The inverter shuts down when the battery reaches ...

Page 12: ...3 UPS Structure 1 3 1 UPS Configuration The UPS configuration is provided in Table 1 1 Table1 1 UPS Configuration Item Components Quantity Remark Standard Backup Type Circuit Breakers 5 Standard Dual Input 1 Standard Parallel Card 1 Optional SNMP Card 1 Optional Long Backup Type Circuit Breakers 4 Standard Dual Input 1 Standard Parallel Card 1 Optional SNMP Card 1 Optional 1 3 2 UPS Outlook The UP...

Page 13: ...5 HSTP3T 15 20KE C KEBC C User Manual Chapter 1 Product Introduction Fig 1 8 System outlook Fig 1 9 15 20 kVA back appearance ...

Page 14: ...will reduce the battery capacity The battery will generate a little amount of hydrogen and oxygen at the end of charging ensure the fresh air volume of the battery installation environment must meet EN50272 2001 requirements If external batteries are to be used the battery circuit breakers or fuses must be mounted as close as possible to the batteries and the connecting cables should be as short a...

Page 15: ...T 15 20KE C KEBC C User Manual Chapter 2 Installation Instruction Fig 2 1 1 Size of the Long Backup Type Unit mm Fig 2 1 2 Size of the standard backup Type Unit mm Fig 2 2 Room reserved for the cabinet Unit mm ...

Page 16: ...eries Included 15kVA 20kVA Long Backup Type 31kg 2 2 Unloading and Unpacking 2 2 1 Moving and Unpacking of the Cabinet The steps to move and unpack the cabinet are as follows 1 Check if any damages to the packing If any contact to the carrier 2 Transport the equipment to the designated site by forklift as shown in Fig 2 3 Fig 2 3 Transport to the designated site 3 Unpack the package see Fig 2 4 Fi...

Page 17: ...act to the carrier b Check the UPS with the list of the goods If any items are not included in the list contact to our company or the local office 6 Dismantle the bolt that connects the cabinet and wooden pallet after disassembly 7 Move the cabinet to the installation position Attention Be careful while removing to avoid scratching the equipment Attention The waste materials of unpacking should be...

Page 18: ...ing structure is in good condition and the mounting floor is smooth and strong 2 Retract the anchor bolts by turning them counterclockwise using wrench the cabinet is then supported by the four wheels 3 Adjust the cabinet to the right position by the supporting wheels 4 Put down the anchor bolts by turning them clockwise using wrench the cabinet is then supported by the four anchor bolts 5 Ensure ...

Page 19: ... wiring diagram Danger The battery terminal voltage is of more than 200Vdc please follow the safety instructions to avoid electric shock hazard Ensure the positive negative neutral electrode is correctly connected from the battery unit terminals to the breaker and from the breaker to the UPS system 2 5 Cable Entry Cables can enter the UPS cabinet from the side or from the bottom Cable entry is mad...

Page 20: ...for power cables are only for situations described below Ambient temperature 30 AC loss less than 3 DC loss less than 1 The length of the AC power cables are no longer than 50 m and the length of the DC power cables are no longer than 30 m Currents listed in the table are based on the 208V system Line to line voltage The size of neutral lines should be 1 5 1 7 times the value listed above when the...

Page 21: ...hese switches to prevent unauthorized operation 2 Open the back door of the cabinet remove the plastic cover The input and output terminal battery terminal and protective earth terminal are shown in Fig 2 9 Fig 2 9 connections terminals 3 Connect the protective earth wire to protective earth terminal PE 4 Connect the AC input supply cables to the Input terminal and AC output supply cables to the O...

Page 22: ...elligent card interface and USB port as it is shown in Fig 2 10 Fig 2 10 Dry contact communication interface 2 7 1 Dry Contact Interface Dry contact interface includes port J2 J11 and the functions of the dry contact are shown in Table 2 5 Table 2 5 Functions of the port Port Name Function J2 1 TEMP_BAT Detection of battery temperature J2 2 TEMP_COM Common terminal for temperature detection J3 1 E...

Page 23: ...ut dry contact Normally closed function is settable Default Fault alarming J9 2 GENERAL_ALARM_NO Output dry contact Normally open function is settable Default Fault alarming J9 3 GENERAL_ALARM_GND Common terminal for J9 1 and J9 2 J10 1 UTILITY_FAIL_NC Output dry contact Normally closed function is settable Default Utility abnormal alarming J10 2 UTILITY_FAIL_NO Output dry contact Normally open fu...

Page 24: ...or contact the local maintenance engineers when placing an order Remote EPO Input Port J4 is the input port for remote EPO It requires shorting NC and 24V and disconnecting NO and 24V during normal operation and the EPO is triggered when opening NC and 24V or shorting the NO and 24V The port diagram is shown in Fig 2 12 and port description is shown in Table 2 7 EPO_NC 24V 24V J4 EPO_NO 24V 24V 24...

Page 25: ...nection of generator Port Name Function J5 1 24V_DRY 24V J5 2 GEN_CONNECTED Connection status of generator J5 3 GND_DRY Power ground for 24V BCB Input Port The default function of J6 and J7 are the ports of BCB The port diagram is shown in Fig 2 14 and description is shown in Table 2 9 BCB_DRV BCB_CONT J6 J7 BCB_ONL 24V 24V 24V Fig 2 14 BCB Port Table 2 9 Description of BCB port Port Name Function...

Page 26: ...Port Name Function J8 1 BAT_LOW_ALARM_NC Battery warning relay normally closed will be open during warning J8 2 BAT_LOW_ALARM_NO Battery warning relay normally open will be closed during warning J8 3 BAT_LOW_ALARM_GND Common terminal General Alarm Output Dry Contact Interface The default function of J9 is the general alarm output dry contact interface When one or more warnings are triggered an aux...

Page 27: ...re warning dry contact interface description Port Name Function J10 1 UTILITY_FAIL_NC Mains failure warning relay normally closed will be open during warning J10 2 UTILITY_FAIL_NO Mains failure warning relay normally open will be closed during warning J10 3 UTILITY_FAIL_GND Common terminal 2 7 2 Communication Interface RS232 RS485 and USB port Provide serial data which can be used for commissionin...

Page 28: ... for communication port RS_232 RS_485 COMM Set Modbus COMM Set SNT Pin Signal Description Pin Signal 1 DCD Data Carrier Detect 1 485_ 2 TXD Transmit Data 2 485_ 3 RXD Receive Data 3 GND 4 DTR Data Terminal Ready 4 5 GND Ground 5 6 DSR Data set Ready 6 7 RTS Request to Send 7 8 CTS Clear to Send 8 9 RI Ring indicator 9 ...

Page 29: ... LED indicator control and operation keys and LCD screen 3 2 1 LED Indicator There are 6 LEDs on the panel to indicate the operating status and fault See Fig 3 1 The description of indicators is shown in Table 3 1 Table 3 1 Status description of indicators Indicators State Description Rectifier indicator Steady green Rectifier normal Flashing green Rectifier normal for at least one module mains no...

Page 30: ...time is out or output short or output no power supply Flashing red Overload output of UPS Off No output of UPS Status indicator Steady green Normal operation Steady red Failure There are two different types of audible alarm during UPS operation as shown in Table 3 2 Table 3 2 Description of audible alarm Alarm Description Two short alarm with a long one When system has general alarm for example AC...

Page 31: ...ecord Menu Fig 3 2 Home page The description of LCD icons is shown in Table 3 4 Table 3 4 Description of LCD Icons Icon Description Power On Off button Parameters of Main Bypass Input History log Function set Fault Clear Battery Test Battery Maintenance language set Manual Transfer etc System Configuration For Service Engineer Only Parameters of Battery DC bus information Temperature etc Parameter...

Page 32: ...t the icon of it will display the information of battery as shown in Fig 3 4 BATTERY P 1 Batt Boost Dischag Times 10 40 NEXT HOME Batt Number Status Batt Volt 5 0 A Batt Curr 240 0 V 240 0 V 5 0 A Fig 3 4 Battery Information Select to view the current status of the UPS Select to turn off the buzzer raising from general alarms Select to view the system information and maintenance code Note The LCD ...

Page 33: ... Menu item Meaning Main input V phase V Voltage I phase A Current Freq Hz Frequency PF Power factor Bypass input V phase V Voltage Freq Hz Frequency I phase A Current PF Power factor Output V phase V Voltage I phase A Current Freq Hz Frequency PF Power factor Load of UPS Sout kVA Apparent Power Pout kW Active Power Qout kVAR Reactive Power Load Load percent Battery data Environmental Temp Environm...

Page 34: ... the test including maintenance test capacity test UPS system information Monitoring software version Monitoring software version Rectified software version Rectifier software version Inverted software version Inverter software version Serial No The serial NO set when delivered from the factory Rated information System rated information 3 5 Event List The following Table3 7 gives events of UPS His...

Page 35: ... disappears 30 Exceed Tx Times Lmt Set Transfer times from inverter to bypass in 1 hour exceed the limit 31 Exceed Tx Times Lmt Clear Incident above disappears 32 Output Short Circuit Set Output shorted Circuit 33 Output Short Circuit Clear Incident above disappears 34 Battery EOD Set Battery End Of Discharge 35 Battery EOD Clear Incident above disappears 36 Battery Test Set Battery Test Starts 37...

Page 36: ...ove disappears 70 Manual Shutdown Set Manually Shutdown 71 Manual Boost Charge Set Manually Battery Boost Charge 72 Manual Float Charge Set Manually Battery Float Charge 73 UPS Locked Set Inhibit to shut down the UPS 74 Parallel Cable Error Set Parallel cable in error 75 Parallel Cable Error Clear Incident above disappears 76 Lost N X Redundant Lost N X Redundant 77 N X Redundant Lost Clear Incide...

Page 37: ...nt above disappears 97 Relay Short Circuit Set Relay shorted 98 Relay Short Circuit Clear Incident above disappears 99 No Inlet Temp Sensor Set The inlet temperature sensor is not connected or abnormal 100 No Inlet Temp Sensor Clear Incident above disappears 101 No Outlet Temp Sensor Set The Outlet temperature sensor is not connected or abnormal 102 No Outlet Temp Sensor Clear Incident above disap...

Page 38: ...ifier indicator goes steady green presenting the finishing of rectification and bypass static switch closes then the inverter is starting up The LED indicators are listed below in Table 4 2 Table 4 2 Inverter starting up Indicator Status Indicator Status Rectifier green Inverter green flashing Battery red Load green Bypass green Status red 6 The UPS transfers from the bypass to inverter after the ...

Page 39: ...on of and then select Manual ESC the system transfer to Normal Mode Note Normally the system will transfer to the Normal mode automatically This function is used when the frequency of the bypass is over track and when the system needs to transfer to Normal mode by manual 4 2 4 Switching the UPS into Maintenance Bypass Mode from Normal Mode These following procedures can transfer the load from the ...

Page 40: ...breakers and bypass static switch will be turned on in 30S after the LED screen goes on the bypass indicator goes green and the load is powered through maintenance bypass and static bypass 2 Turn off the maintenance bypass switch and fix the protection cover and then the load is powered through bypass static switch 3 Select the icon of and select Fault Clear to turn on the inverter 4 After 60S the...

Page 41: ...e flood etc To achieve this just press the EPO button and the system will turn off the rectifier inverter and stop powering the load immediately including the inverter and bypass output and the battery stops charging or discharging If the input utility is present the UPS control circuit will remain active however the output will be turned off To completely isolate the UPS users need to open the ex...

Page 42: ...peration System 4 5 1 Parallel system diagram Up to four UPS could be paralleled with a diagram as shown in Fig 4 6 UPS1 Load Connected Output Power Supply Power Supply UPS2 UPS3 UPS4 Fig 4 6 Parallel diagram The parallel board is located at the back of the UPS cabinet as is shown in Fig 4 7 ...

Page 43: ...E C KEBC C User Manual A Fig 4 7 Location of the Parallel board All the parallel cables are designed to be shielded and double insulated and are connected between the UPS to form a loop as shown below in Fig 4 8 Fig 4 8 Parallel connection ...

Page 44: ...the High Leakage Current Warning in the first part of this manual 4 The outputs of all UPS must be connected to a common output bus Parallel system software setting To change the parallel system setting please follow the steps below 1 With the monitoring software from manufacturer select the page of Service Setting as below Set System Mode to Parallel and set the United Number to the number of uni...

Page 45: ...Chapter 4 Operations 37 HSTP3T 15 20KE C KEBC C User Manual Fig 4 11 Connectors on Parallel board PS1409_TF1 Fig 4 12 Connectors on Control board PS1203_CT1 ...

Page 46: ...parallel keep all the connectors J21 J25 open As is shown in Fig 4 12 Note The connectors not mentioned keep them untouched When all the connection and settings are finished follow the steps below for the operation of parallel system setup 1 Close the output and input breaker of the first unit Wait for the startup of bypass static switch and rectifier about 90 seconds later the system will transfe...

Page 47: ...mainly determined by the following factors 1 Installation The battery should be placed in dry and cool place with good ventilation Avoid direct sunlight and keep away from heat source When installing ensure the correct connection to the batteries with same specification 2 Temperature The most suitable storage temperature is 20 ºC to 25ºC The battery life will be shortened if the battery is used un...

Page 48: ...ead acid battery should be recycled and reused and it is prohibited to dispose of the batteries in other ways except recycling Throwing away the waste lead acid batteries at will or other improper disposal methods will cause severe environment pollution and the person who does this will bear the corresponding legal responsibilities 5 3 1 Installation of internal battery For 15kVA to 20kVA standard...

Page 49: ...3 Connect the battery cable according to the series number 4 Recover the cover Fig 5 1 Installation of inner battery for15 20K standard UPS Warning Make sure the polarity of the battery is correct according to the diagrams above Test and confirm the battery voltage before connectting to the main circuit ...

Page 50: ...1 Note The above mentioned product standards incorporate relevant compliance clauses with generic IEC and EN standards for safety IEC EN AS60950 electromagnetic emission and immunity IEC EN AS61000 series and construction IEC EN AS60146 series and 60950 Warning This product conform the EMC requirements for UPS in Category C3 and it is not suitable for medical equipment 6 2 Environmental Characteri...

Page 51: ...Parameters Battery bus voltage Vdc Rated 240V Quantity of lead acid cells Nominal 40 1 battery 12V 240 1 battery 2V Float charge voltage V cell VRLA 2 25V cell selectable from 2 2V cell 2 35V cell Constant current and constant voltage charge mode Temperature compensation mV cl 3 0 selectable 0 5 0 Ripple voltage 1 Ripple current 5 Equalized charge voltage VRLA 2 4V cell selectable from 2 30V cell ...

Page 52: ... 20 80 20 Transient recovery 30ms for step load 20 100 20 Output Voltage THDu 1 from 0 to 100 linear load 6 full non linear load according to IEC EN62040 3 6 4 4 Electrical Characteristics Bypass Mains Input Table 6 8 Bypass Mains Input Item Unit Value Rated AC voltage Vac 380 400 415 three phase four wire and sharing neutral with the bypass Overload 125 Long term operation 125 130 for 10min 130 1...

Page 53: ... power kVA Unit 15 20kVA Overall efficiency Normal mode dual conversion 95 Battery discharging efficiency battery at nominal voltage 480Vdc and full rated linear load Battery mode 94 5 6 6 Display and Interface Table 6 10 Display and Interface Display LED LCD Interface Standard RS232 RS485 Option SNMP Dry Contact ...

Reviews: