11
HSTP3T 15/20KE-C/KEBC-C User Manual
Chapter 2 Installation Instruction
2.4 Battery
Three terminals
(
positive
,
neutral
,
negative
)
are drawn from the battery unit and connected
to UPS system. The neutral line is drawn from the middle of the batteries in series (See
Fig.2-7).
+
-
N
N
40 batteries in series
40
39
21
Fig.2-7 Battery string wiring diagram
Danger
The battery terminal voltage is of more than 200Vdc, please follow the safety instructions to
avoid electric shock hazard.
Ensure the positive, negative, neutral electrode is correctly connected from the battery unit
terminals to the breaker and from the breaker to the UPS system.
2.5 Cable Entry
Cables can enter the UPS cabinet from the side or from the bottom. Cable entry is made
possible through a blanking plate fitted at the bottom of the equipment. The cable entry is
shown in Fig.2-8.
Fig.2-8 Cable entry