Chapter 2 Installation Instruction
16
HSTP3T 15/20KE-C/KEBC-C User Manual
J2
J3
T
E
M
P
_
B
A
T
T
E
M
P
_
E
N
V
Fig.2-11 J2 and J3 for temperature detecting
Table 2.6 Description of J2 and J3
Port
Name
Function
J2-1
TEMP_BAT
Detection of battery temperature
J2-2
TEMP_COM
Common terminal
J3-1
ENV_TEMP
Detection of environmental temperature
J3-2
TEMP_COM
Common terminal
Note
Specified temperature sensor is required for temperature detection (R25=5Kohm,
B25/50=3275), please confirm with the manufacturer, or contact the local maintenance
engineers when placing an order.
Remote EPO Input Port
J4 is the input port for remote EPO. It requires shorting NC and +24V and disconnecting
NO and +24V during normal operation, and the EPO is triggered when opening NC and +24V
or shorting the NO and +24V. The port diagram is shown in Fig.2-12, and port description is
shown in Table 2.7.
E
P
O
_
N
C
+
2
4
V
+24V
J4
EP
O
_
N
O
+
2
4
V
+24V
+24V
Fig.2-12 Diagram of input port for remote EPO
Table 2.7 Description of input port for remote EPO
Port
Name
Function
J4-1
REMOTE_EPO_NC
Trigger EPO when disconnect with J4-2
J4-2
+24V_DRY
+24V
J4-3
+24V_DRY
+24V
J4-4
REMOTE_EPO_NO
Trigger EPO when connect with J4-3
Generator Input Dry Contact
Summary of Contents for HSTP3T15KE-C