Chapter 3 LCD Panel
26
HSTP3T 15/20KE-C/KEBC-C User Manual
Menu
name
Menu item
Meaning
alarm
on LCD
History log
Display all history logs.
Function
Settings
Display calibration
Adjust the accuracy of LCD display
Date format set
MONTH-DATE-YEAR and YEAR-MONTH-DATE
formats can be selected
Date & Time
Date/Time set
Language set
User can set the language
Communication set
/
Control password 1
set
User can modify control password 1
Command
Battery maintenance
test
This test will lead to the battery being partly
discharged to activate battery until battery voltage is
low. Bypass must be in normal condition, the battery
capacity should be above 25%.
Battery self-check
test
UPS transfer to battery discharge mode to test if the
battery is normal. Bypass must be in normal
condition, the battery capacity should be above 25%.
Stop testing
Manually Stop the test including maintenance test,
capacity test
UPS
system
information
Monitoring software
version
Monitoring software version
Rectified software
version
Rectifier software version
Inverted software
version
Inverter software version
Serial No.
The serial NO set when delivered from the factory
Rated information
System rated information
3.5 Event List
The following Table3.7 gives events of UPS History Log
Table 3.7 List of History Log
String
Sequence
LCD Display
Explanation
1
Load On UPS-Set
Load On UPS
2
Load On Bypass-Set
Load On Bypass
3
No Load-Set
No Load (Output Power Lost)
4
Battery Boost-Set
Charger is Boosting Battery Voltage
5
Battery Float-Set
Charger is Floating Battery Voltage
6
Battery Discharge-Set
Battery is Discharging
7
Battery Connected-Set
Battery cables Connected
8
Battery Not Connected-Set
Battery cables Disconnected.
9
Maintenance CB Closed-Set
Maintenance CB is Closed
10
Maintenance CB Open-Set
Maintenance CB is Open
11
EPO-Set
Emergency Power Off
12
Less-Set
Valid Inverter capacity is less than the load