LIMITED WARRANTY AND CONNECTED EQUIPMEN GUARNTEE 

TECHNICAL SPECIFICATIONS

TROUBLE SHOOTIMG

LCD STATUS AND SETUP FUCTIONS

   

1. 

General Mode: 

a. Press the “Display” button to check the status of the UPS. 
b. Press and hold the 

Display

 toggle for 4 seconds, 

-If the machine is in the Battery Mode, it enters the status of Mute.

 

- If the machine is in the Line Mode, it proceeds Self Test.

 

c. If the 

Display

 toggle remains untouched for over 30 seconds, the LCD 

backlight will turn off automatically. 

 

2.

 Set-up Mode

 

Step 1:

 The machine enters Set-Up Mode after holding the Display toggle for 10 

seconds. Icon 3,4,5,6,7,8 lights to indicate Set-Up Mode. 

Step 2:

 By pressing the Display toggle, users can switch between setup 

functions. User configurable functions are as follows: 
 

a.  Delay Time: The time delay between switching from Battery Mode to Line Mode. There are 9 different settings. The default 

setting is 0 minutes.

 

 

b.  Battery Pack Numbers: This function provides the estimated UPS runtime using various numbers of battery packs. The default 

setting is 0. 

c.  Static Frequency Tolerance: There are 6 settings. The default setting is +/-6%.

Functional description:

 The setting may be 

adjusted to the quality of the electricity in use 

d.  Slew rate: also called Dynamic Frequency Tolerance. There are 5 different settings. The fault value is 4Hz/sec.

 Functional 

Description:

 “Slew Rate” indicates the tolerance of a device in accepting frequency variance. The lower “Slew Rate” results in 

less tolerance but better protection for the connected loads. 

e.  Battery Shutdown Voltage: This function adjusts the UPS shutdown point according to the battery voltage. 
 

The settable items are sorted by unit as in the following table

 

Step 3: 

Press and hold the toggle for 4 seconds. When the icons blink, the value of 

each item can be changed by slightly pressing the toggle. 

Step 4: 

To save the value and return to general mode, press and hold the toggle for 

4 seconds. 

 

Note: If the machine is left idle for over 30 seconds during setup, it will turn 
off the backlight and return to general mode automatically.   

 

Note: If user wants to return to general mode without saving changes, there are two methods: 

1.  Wait for the backlight to turn off 
2.  Press and hold the “Display” toggle for 10 seconds 

 

 

 

Problem

 

Possible Cause 

Solution

 

Circuit breaker has tripped 
due to an overload. 

Turn the UPS off and unplug at least one piece of equipment. 
Wait 10 seconds, reset the circuit breaker by depressing the 
button, and then turn the UPS on.

 

Batteries are discharged 

Recharge the unit for at least 4 hours 

Unit has been damaged by a 
surge or spike.   

Contact CyberPower Systems about replacement batteries at 

tech@cpsww.com 

 

Outlet do not provide power 
to equipment

 

Uncritical outlets have 
turned off automatically   
due to an overload 

Push the toggle button to make the uncritical outlets turn on. 

Battery not fully charged. 

Recharge the battery by leaving the UPS plugged in. 

The UPS does not perform 
expected runtime. 

Battery is degraded 

Contact CyberPower Systems about replacement batteries at 

tech@cpsww.com 

 

The on/off switch is designed 
to prevent damage by rapidly   
turning it off and on. 

Turn the UPS off. Wait 10 seconds and then turn the 
 UPS on. 

The unit is not connected to   
an AC outlet. 

The unit must be connected to a 110/120v outlet. 

The battery is worn out. 

Contact CyberPower Systems about replacement batteries at 

tech@cpsww.com 

 

The UPS will not turn on. 
 

Mechanical problem. 

Contact CyberPower Systems at 

tech@cpsww.com 

 

The serial cable or USB cable 
is not connected. 

Connect the cable to the UPS unit. You must use the cable that 
came with the unit. 

The cable is connected to the 
wrong port. 

Try another port of your computer 

The unit is not providing   
battery power. 

Shutdown your computer and turn the UPS off.  Wait 10 
seconds and turn the UPS back on. This should reset   
the unit. 

PowerPanel

®

 Personal   

Edition is inactive 

The serial cable is not the 
cable that was provided   
with the unit. 

You must use the cable included with the unit for the 
software 

Additional troubleshooting information can be found at 

www.cyberpowersystems.com/support.htm

 

 

 

 

Model 

PR1000LCDRT2U 

PR1500LCDRT2U 

PR2200LCDRT2U 

PR1000LCDRTXL2U

Capacity(VA) 

1000 

1500 

2170 

1000 

Capacity(Watts) 700 

1000 

1600 

700 

Input 

Input Voltage Range 

80Vac-150Vac 

Input Frequency Range 

50/60Hz+/-3Hz(auto sensing) 

Output 

On Battery Output Voltage 

Pure Sine Wave at /-7% 

On Battery Output Frequency 

50/60+/-1% 

Transfer Time(Typical) 

4 ms 

Overload Protection 

On Utility: Circuit Breaker, On Battery: Intemal Current Limiting   

Surge Protection and Filtering 

Lightning/Surge Protection 

Yes 

Internet Ready(DSL/Phone/ 
FAX/Modem Protection) 

RJ11/RJ45(One In/One Out) 

Physical 

Output Receptacles 

Dimensions(cm) 

2U Rack, 43.3 x 8.8 x 38.8 

Weight (Kg) 

26.6 

27 

30 

30 

Battery  

Sealed Maintenance Free Lead 
Acid Battery 

   

12V / 7.0AHx4 

12V / 9.0AHx4 

12V / 9.0AHx4 

Extended runtime 

Hot Swappable Extemal Battery 

Yes 

Warning Diagnostics 

Indicators 

Power On, Wiring Fault, LCD Display (Using Battery, AVR, Load Level, Battery Level) 

Audible Alarms 

On Battery, Low Battery, Overload 

Environmental  

Operating Temperature 

32

to 104

( 0

to40

 ) 

Operating Relative Humidity 

0 to 95% Non-Condensing 

Communication 

PowerPanel 

®

Business Edition

 

 

Windows 98/ME/NT/2000/XP, Vista 

Management 

Self-Test  

Manual Self-Test 

Auto-Charger/ Auto-Restart 

Yes 

COM Interface 

True RS232 x1+ Contact Closure x1 

Built-in USB Interface 

Yes 

SNMP/ HTTP Network Slot  

Yes 

Safety Approvals 

UL1778,cUL107,FCC/Doc Class B 

 

 
 

 

GreenPower UPS™ 

The CyberPower GreenPower UPS™ cuts UPS energy costs by up to 75% compared to the conventional UPS 
circuits. Conventional UPS systems pass power through a transformer to provide normal output voltage to protected 
devices. By contrast, the GreenPower UPS™ circuitry bypasses the transformer when utility power is normal, 
significantly increasing the power efficiency of the UPS. As a result, a GreenPower UPS™ produces less heat and 
uses less energy reducing energy costs. 
When utility power is abnormal, the GreenPower UPS™ operates like a normal UPS. Since utility power operates 
normally 88% of the time, the GreenPower UPS™ operates primarily in its cost-cutting bypass mode.   

 

 

 

Read the following terms and conditions carefully before using the CyberPower

 PR1000LCDRT2U/PR1000LCDRTXL2U/PR1500LCDRT2U/ 

PR2200LCDRT2U 

(the "Product"). By using the Product you consent to be bound by and become a party to the terms and conditions of this 

Limited Warranty and Connected Equipment Guarantee (together referred to as this "Warranty"). If you do not agree to the terms and conditions 
of this Warranty, you should return the Product for a full refund prior to using it.

 

 
Who is Providing this Warranty? 

CyberPower Systems (USA), Inc. ("CyberPower") provides this Limited Warranty. 

 
What Does This Warranty Cover? 

This warranty covers defects in materials and workmanship in the Product under normal use and conditions.    It also covers equipment that was 
connected to the Product and damaged because of the failure of the Product. 

 
What is the Period of Coverage? 

This warranty covers the Product for three years and connected equipment for as long as you own the Product. 

 
Who Is Covered? 

This warranty only covers the original purchaser.    Coverage ends if you sell or otherwise transfer the Product. 

 
How Do You Get Service?

 

1. Call us at (877) 297-6937 or write to us at Cyber Power Systems (USA), Inc., 4241 12th Ave. E., STE 400, Shakopee, MN 55379 or send us an 
e-mail message at claims@cpsww.com for instructions. 
2. When you contact CyberPower, identify the Product, the Purchase Date, and the item(s) of Connected Equipment. Have information on all 
applicable insurance or other resources of recovery/payment that are available to the Initial Customer and Request a Claim Number. 
3. You must provide a 

dated Proof-of-Purchase receipt

 (or other proof of the original purchase) and provide a description of the defect. 

4. Pack and ship the product with a 

dated Proof- of-Purchase receipt

 to CyberPower and, if requested, the item(s) of Connected Equipment, a 

repair cost estimate for the damage to the Connected Equipment, and all claim forms that CyberPower provides to you. Show the Claim Number 
on the shipping label or include it with the product.

 You must prepay all shipping costs, you are responsible for packaging and shipment, 

and you must pay the cost of the repair estimate. 
 
How Long Do I Have To Make A Claim?   

All claims must be made within ten days of the occurrence. 

 
What Will We Do To Correct Problems? 

CyberPower will inspect and examine the Product.   
If the Product is defective in material or workmanship, CyberPower will repair or replace it at CyberPower's expense, or, if CyberPower is unable 
to or decides not to repair or replace the Product (if defective) within a reasonable time, CyberPower will refund to you the full purchase price you 
paid for the Product (purchase receipt showing price paid is required).     
If it appears that our Product failed to protect any equipment plugged into it, we will also send you forms for making your claim for the connected 
equipment.    We will repair or replace the equipment that was damaged because of the failure of our Product or pay you the fair market value 
(NOT REPLACEMENT COST) of the equipment at of the time of the damage.    We will use Orion Blue Book, or another a third-party valuation 
guide, or eBay, craigslist, or other source to establish that amount. 

 

Our maximum liability is limited to

 $400,000 for PR1000LCDRT2U/ 

PR1000LCDRTXL2U/ PR1500LCDRT2U/ PR2200LCDRT2U

.

 

 
Who Pays For Shipping? 

We pay when we send items to you; you pay when you send items to us.   

 
What Are Some Things This Warranty Does Not Cover? 

1. This Warranty does not cover any software that was damaged or needs to be replaced due to the failure of the Product or any data that is lost 
as a result of the failure or the restoration of data or records, or the reinstallation of software. 
2. This Warranty does not cover or apply to: misuse, modification, operation or storage outside environmental limits of the Product or the 
equipment connected to it, nor for damage while in transit or in storage, nor if there has been improper operation or maintenance, or use with 
items not designed or intended for use with the Product, such as laser printers, appliances, aquariums, medical or life support devices, etc.   

 
What Other Limitations Apply? 

1. This Warranty does not apply unless the Product and the equipment that was connected to it were connected to properly wired and grounded 
outlets (including compliance with electrical and safety codes of the most current electrical code), without the use of any adapters or other 
connectors. 
2. The Product must have been plugged directly into the power source and the equipment connected to the Product must be directly connected 
to the Product and not "daisy-chained" together in serial fashion with any extension cords, another Product or device similar to the Product, surge 
suppressor, or power tap.    Any such installation voids the Limited Warranty. 
3. The Product and equipment connected to it must have been used properly in a suitable and proper environment and in conformance with any 
license, instruction manual, or warnings provided with the Product and the equipment connected to it. 
4. The Product must have been used at all times within the limitations on the Product's VA capacity. 

 
What are the Limitations?   

The sole and exclusive remedies of the Initial Customer are those provided by this Warranty. 
The Product was designed to eliminate disrupting and damaging effects of momentary (less than 1ms) voltage spikes or impulses from lightning 
or other power transients.    If it can be shown that a voltage spike lasting longer than 1ms has occurred, the occurrence will be deemed outside 
the rated capabilities of the Product and the Limited Warranty is void. CyberPower Does Not Cover or Undertake Any Liability in Any Event for 
Any of the Following: 
1. Loss of or damage to data, records, or software or the restoration of data or records, or the reinstallation of software. 
2. Damage from causes other than AC Power Line Transients, spikes, or surges on properly installed, grounded and code-compliant 120 volt 
power lines in the United States and Canada; transients, surges or spikes on standard telephone land lines, PBX telephone equipment lines or 
Base 10T Ethernet lines, when properly installed and connected. (This exclusion applies, for example, to fluctuations in data transmission or 
reception, by CATV or RF transmission or fluctuations, or by transients in such transmission.) 
3. Damage from any circumstance described as excluded above with respect to the Product. 
4. Damages from fire, flood, wind, rain, rising water, leakage or breakage of plumbing, abuse, misuse or alteration of either the product or the 
Connected Equipment. 
5. CyberPower excludes any liability for personal injury under the Limited Warranty and Connected Equipment Guarantee. CyberPower excludes 
any liability for direct, indirect, special, incidental or consequential damages, whether for damage to or loss of property [EXCEPT FOR (AND 
ONLY FOR) the specific limited agreement of CyberPower to provide certain warranty benefits regarding "Connected Equipment" under this 
Warranty], loss of profits, business interruption, or loss of information or data. NOTE: Some States or Provinces do not allow the exclusion or 
limitation of incidental or consequential damages, so the above limitation may not apply to you. 
6. The Product is not for use in high-risk activities or with aquariums. The Product is not designed or intended for use in hazardous environments 
requiring fail-safe performance, or for use in any circumstance in which the failure of the Product could lead directly to death, personal injury, or 
severe physical or property damage, or that would affect operation or safety of any medical or life support device (collectively, "High Risk 
Activities"). CyberPower expressly disclaims any express or implied warranty of fitness for High Risk Activities or with aquariums. CyberPower 
does not authorize use of any Product in any High Risk Activities or with Aquariums. 

ANY SUCH USE IS IMPROPER AND IS A MISUSE OF 

THE PRODUCT. 
 
What is the Fine Print?     

The application of the United Nations Convention of Contracts for the International Sale of Goods is expressly excluded. 
CyberPower is the warrantor under this Limited Warranty.   
For further information please feel free to contact CyberPower at Cyber Power Systems (USA), Inc. 4241 12th Ave E., STE 400, Shakopee, MN 
55379; call us at (877) 297-6937; or send us an e-mail message at claims@cpsww.com. 

 

FCC Notice 

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1)This device 
may not cause harmful interference, and (2) this device must accept any interference received, including interference that 
may cause undesired operation. 

 

WARNING!!

 This equipment has been tested and found to comply with the limits for a Class B Digital Device, pursuant to Part 15 of the FCC 

Rules.  These limits are designed to provide reasonable protection against harmful interference in residential installation.  This equipment 
generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful 
interference to radio communications.  However, there is no guarantee that interference will not occur in a particular installation.  If this 
equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the 
user is encouraged to try to correct the interference by one or more of the following measures:    (1) Reorient or relocate the receiving antenna.   
(2) Increase the separation between the equipment and receiver.    (3) Connect the equipment into an outlet on a circuit different from that to 
which the receiver is connected.      (4) Consult the dealer or an experienced radio/TV technician for help.    Any special accessories needed for 
compliance must be specified in the instruction.     
 
 
 

 

 

 Item 

Unit 

1 Input 

Voltage 

2 Output 

Voltage 

3 Output 

Frequency 

Hz 

4 Load 

Kw 

5 Estimate 

Run 

Time 

 

Min 

6 Load 

Capacity 

7 Battery 

Capacity 

8 Centigrade 

 

9 Fahrenheit 

 

Items Unit 

Delay Time 

Min 

Battery Pack Numbers 

Static Frequency Tolerance 

Slew Rate 

Hz 

Battery Shutdown Voltage 

CYBERPOWER GREENPOWER UPS™ TECHNOLOGY 

The Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulation. 
 
Cet appareil numerique de la class B respecte toutes les exigencies du Reglement sur le materiel brouilleur du Canada

 