INTRODUCTION CONT.
[NOTE] MBP63A2 Only with compatible CyberPower UPS.
[NOTE] If the UPS model name is OL6KRT/OL8KRT/OL10KRT/OL6KRTF/OL8KRTF/OL10KRTF,
Please check the MCU version* on LCD Panel by the following operations.
1. Press the “ENTER” button to enter the “Main Menu”.
2. Press the “
▲
” and “
▼
” buttons to scroll to the “Information” option.
3. Press the “ENTER” button to select the “Information” submenu.
4. Press the “
▲
” and “
▼
” buttons to scroll through the “Information” submenu to check the MCU version*.
[NOTE] If the MCU version* is UE_V3Rn and the number of n is less than 6,(For Example: MCU Ver.
= UE_V3R5) Please contact CyberPower for assistance to upgrade the MCU version*.
[NOTE]*MCU version is the UPS Firmware version.
[NOTE] If the MBP Detection Cable is not used, the Firmware is not required to be updated.
[NOTE] If MBP Detection Cable is installed, the UPS EPO and ROO functions will be disabled.
[NOTE] If MBP Detection Cable is not installed, the UPS will not automatically transfer to bypass mode.
[NOTE] TO AVOID DAMAGE! Read the MBP User Manual before installation and operation for
correct operating procedures and to avoid lost power load or UPS damage.
[NOTE] If the UPS is equipped with outlets, those outlets can no longer be used, loads can only be
connected to the MBP outlets or the MBP Output terminal blocks.
UPS should be turned off when UPS is doing maintenance, if load connect to UPS outlet, the load
will be lost.
Before turn off UPS, MBP need to set to bypass and keep provide power from utility.