IMPORTANT SAFETY INSTRUCTIONS

 

 

1

 

 

 

This manual contains important instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual 
thoroughly before attempting to unpack, install, or operate the UPS. 

 

CAUTION!   

The  UPS  must  be  connected  to  a  grounded  AC  power 

outlet with fuse or circuit breaker protection. DO NOT plug the UPS into 
an outlet that is not grounded. If you need to power-drain this equipment, 
turn off and unplug the unit.

 

CAUTION!   

The  battery  can  power  hazardous  components  inside  the 

unit, even when the AC input power is disconnected.

 

CAUTION!   

The UPS should be placed near the connected equipment 

and easily accessible. 

CAUTION!   

To  prevent  the  risk  of  fire  or  electric  shock,  install  in  a 

temperature  and  humidity  controlled  indoor  area,  free  of  conductive 
contaminants. (Please see specifications for acceptable temperature and 
humidity range).

 

CAUTION!    (No  User  Serviceable  Parts):

  Risk  of  electric  shock,  do 

not  remove  cover.  No  user  serviceable  parts  inside.  Refer  servicing  to 
qualified service personnel.

 

CAUTION!    (Non-Isolated  Battery  Supply): 

Risk  of  electric  shock, 

battery circuit is not isolated from AC power source; hazardous voltage 
may exist between battery terminals and ground. Test before touching.

 

CAUTION!   

To  reduce  the  risk  of  fire,  connect  the  UPS  to  a  branch 

circuit with 40 amperes (OL6000) / 50 amperes (OL8000) / 60 amperes 
(OL10000)  maximum  over-current  protection  in  accordance  to  CE 
requirement.

 

CAUTION!   

The AC outlet where the UPS is connected should be close 

to the unit and easily accessible. 

CAUTION!   

Please use only VDE-tested, CE-marked mains cable, (e.g. 

the mains cable of your equipment), to connect the UPS to the AC outlet.

 

CAUTION!   

Please  use  only  VDE-tested,  CE-marked  power  cables  to 

connect any equipment to the UPS. 

CAUTION!   

When installing the equipment, ensure that the sum of the 

leakage  current  of  the  UPS  and  the  connected  equipment  does  not 
exceed 3.5mA.

 

CAUTION! 

The  OL6000  /  OL8000  /  OL10000  models  are 

permanently-connected  equipment  and  only  qualified  maintenance 
personnel may carry out installations.

 

CAUTION!   

Do not unplug the unit from AC Power during operation, as 

this will invalidate the protective ground insulation. 

CAUTION!   

To avoid electric shock, turn off and unplug the unit before 

installing  the  input/output  power  cord  with  a  ground  wire.  Connect  the 
ground wire prior to connecting the line wires! 

CAUTION!   

Do not  use an improper size power cord  as it may cause 

damage to your equipment and cause fire hazards. 

CAUTION!   

Wiring must be done by qualified personnel.

 

CAUTION!    DO  NOT  USE  FOR  MEDICAL  OR  LIFE  SUPPORT 
EQUIPMENT!

    Under  no  circumstances  this  unit  should  be  used  for 

medical applications involving life support equipment and/or patient care.

 

CAUTION!    DO NOT USE WITH OR NEAR AQUARIUMS!

    To reduce 

the risk of fire, do not use with or near aquariums.    Condensation from 
the  aquarium  can  come  in  contact  with  metal  electrical  contacts  and 
cause the machine to short out. 

CAUTION!   

Do  not  dispose  of  batteries  in  fire  as  the  battery  may 

explode. 

CAUTION!   

Do not open or mutilate the battery, released electrolyte is 

harmful to the skin and eyes. 

CAUTION!   

A battery can present a risk of electric shock and high short 

circuit  current.  The  following  precaution  should  be  observed  when 
working on batteries 
1.

 

Remove watches, rings or other metal objects. 

2.

 

Use tools with insulated handles. 

CAUTION!   

The  unit  has  a  dangerous  amount  of  voltage.  When  the 

UPS  indicators  is  on,  the  units  may  continue  to  supply  power  thus  the 
unit’s outlets may have a dangerous amount of voltage even when it’s not 
plugged in to the wall outlet. 

CAUTION!   

Make  sure  everything  is  turned  off  and  disconnected 

completely before conducting any maintenance, repairs or shipment. 

CAUTION!   

Connect the Protection Earth (PE) safety conductor before 

any other cables are connected. 

WARNING!    (Fuses): 

To  reduce  the  risk  of  fire,  replace  only  with  the 

same type and rating of fuse. 

 

 

DO  NOT  INSTALL  THE  UPS  WHERE  IT  WOULD  BE  EXPOSED  TO 
DIRECT SUNLIGHT OR NEAR A STRONG HEAT SOURCE! 

DO  NOT  BLOCK  OFF  VENTILATION  OPENINGS  AROUND  THE 
HOUSING! 

DO  NOT  CONNECT  DOMESTIC  APPLIANCES  SUCH  AS  HAIR 
DRYERS TO UPS OUTPUT SOCKETS! 

SERVICING  OF  BATTERIES  SHOULD  BE  PERFORMED  OR 
SUPERVISED  BY  PERSONNEL  KNOWLEDGE  OF  BATTERIES  AND 
THE 

REQUIRED 

PRECAUTIONS. 

KEEP 

UNAUTHORIZED 

PERSONNEL AWAY FROM BATTERIES!

 

Summary of Contents for OL10000ERT3UDM

Page 1: ...User s Manual OL6000ERT3UDM OL8000ERT3UDM OL10000ERT3UDM CyberPower Systems Inc www cpsww com K01 0000407 01 ...

Page 2: ...nce personnel may carry out installations CAUTION Do not unplug the unit from AC Power during operation as this will invalidate the protective ground insulation CAUTION To avoid electric shock turn off and unplug the unit before installing the input output power cord with a ground wire Connect the ground wire prior to connecting the line wires CAUTION Do not use an improper size power cord as it m...

Page 3: ...left rail 2 sets Rackmount right rail 2 sets Phone line USB communication cable Serial Interface Cable RS 232 Battery module Rackmount ears Stands 2 2 sets Tie plate 1 1 set Flat head screws M5X8L 8 2 sets Pan head screws M5X12L 12 2 sets Plastic washers 8 2 sets Screw hole dust covers 10 2 sets PowerPanel Business Edition software CD ...

Page 4: ... 36 inches deep Select the proper holes in the rack for positioning the Battery module in the rack The Power module or the Battery module takes up position 1 through position 9 Step 4 Adjust rackmount rails to fit your rack Attach the rackmount rail to your rack with two M5X12L screws and two plastic washers at the front of the rack Located in position 1 position 6 Do not tighten the screws Adjust...

Page 5: ...ear screw holes that are not being used ELECTRICAL INSTALLATION After completing the hardware installation of the UPS you are now ready to plug in the UPS and connect your equipment SAFETY PRECAUTIONS CAUTION Installation environment should be in a temperature and humidity controlled indoor area free of conductive contaminants Do not install this UPS where excessive moisture or heat is present Ple...

Page 6: ...ne fax machine or network device 5 Press the ON OFF switch to turn the UPS on The Power On indicator light will display when activated If an overload is detected an audible alarm will sound and the UPS will continuously emit two beeps per second For resetting the unit unplug some equipment from the outlets Make sure your equipment carries a load current within the unit s safe range refer to the te...

Page 7: ...PUT CONFIGURATION 1 Remove the interconnection wires Jumper on bypass terminals 2 Hardwire the input output terminals as shown in the following diagram L N PE Bypass Circuit Breaker Input Circuit Breaker Wiring AWG Wiring AWG L N PE External EPO Output Mains2 UPS PFC AC DC Inverter DC AC STS Battery N L N L PE J PE L N PE Mains1 N L PE SAFETY PRECAUTIONS CAUTION Input and Output circuit breakers m...

Page 8: ...ock Tighten the two screws to fix the bottom cover on the terminal block Step 3 Bypass configuration for dual input configuration Remove the interconnection wires Jumper on bypass terminals J L and insert the bypass cable through the appropriate cable gland not included Connect the three wires to the bypass terminal block L N G Step 4 Input configuration Insert the input cable through the appropri...

Page 9: ... wires to the input terminal block Step 5 Output configuration Insert the output cable through the appropriate cable gland not included Connect the three wires to the output terminal block Step 6 Fix the top cover on the bottom cover Tighten the two screws to fix the top cover on the bottom cover ...

Page 10: ...r1 Jumper2 on Backfeed Protection Connector UPS L N PSDR AC L AC N IP L IP N Backfeed 1 2 4 5 3 L N I P EMI L N L N PE Mains PE Jumper2 Jumper1 WITH BACKFEED PROTECTION CONFIGURATION 1 Customers should provide an external isolation device Magnetic Contactor which is upstream and outside the UPS and capable of supporting the UPS input current 2 Remove the interconnection wires Jumper1 Jumper2 on Ba...

Page 11: ...ction while the computer can monitor the UPS and alter its various programmable parameters 9 USB port This is a connectivity port which allows communication and control between the UPS and the connected computer It is recommended to install the PowerPanel Business Edition Agent software on the PC Server connected with the USB cord 10 Remote Control Port Connects to remote LCD module to the UPS 11 ...

Page 12: ... this output cable to connect the Battery module to the Power module or to the next Battery module BPE240V30ART3US BPE240V50ART3US CONNECTION 1 POWER MODULE WITH ONE BATTERY MODULE Step 1 Loosen the two screws to remove the battery cable retention bracket of the power module Step 2 Use the output cable of the Battery module to connect the Battery module to the Power module Step 3 Rotate the batter...

Page 13: ...e two screws to remove the battery cable retention bracket of the 1st battery module Step 3 Use the output cable of the 2nd Battery module to connect the 2nd Battery module to the 1st Battery module Step 4 Rotate the battery cable retention bracket and tighten the two screws to fix battery cable Step 5 Use a power cord to plug AC input inlet of the 2nd battery module into AC output outlet of the 1...

Page 14: ...Y Red Battery will soon need to be replaced due to insufficient runtime LCD SCREEN UPS STATUS LCD Screen UPS Status Description Line Mode UPS is operating in Line Mode Battery Mode UPS is operating in Battery Mode Bypass Mode UPS is operating in Bypass Mode Manual Bypass UPS is operating in Manual Bypass ECO Mode UPS is operating in ECO Economy Mode BUTTON OPERATION Button Operation Description ON...

Page 15: ...iption O P Volt XXX XV Displays the Output Voltage O P Freq XX XHz Displays the Output Frequency I P Volt XXX XV Displays the Input Voltage I P Freq XX XHz Displays the Input Frequency O P Load XXX Displays the Output Load Percentage of Maximum load O P Amp X XA Displays the Output Current O P Watt XXXXXW Displays the Output Wattage O P VA XXXXXVA Displays the Output VA BAT Volt XXX XV Displays th...

Page 16: ...n to select the Language submenu 6 Press the and buttons to scroll to the language that you want to select You may be prompted to save the selection if so press the ENTER button to save the setting 7 Press the ESC button to cancel or return to previous LCD menu LCD SETTINGS CONFIGURATION There are 24 UPS settings that can be configured by the user 1 Press the ENTER button to activate the MAIN MENU...

Page 17: ...z O P Freq 60Hz Converter OFF Screen Saver Disable 1 Minutes 5 Minutes 5 minutes Clear Event Log Activate None Button OFF LOCK Disable Enable Disable Charger Function SBM Constant SBM Signal Inputs Disable EPO ROO Disable Charger Check Disable Enable Disable With Transformer Disable Enable Disable Backfeed Check Disable Enable Disable Output voltage default setting depends on different nation or o...

Page 18: ... figure WALL MOUNTING INSTRUCTIONS Step 1 Remove the Multifunction LCD Module Unscrew the right panel of the Power module Separate the right panel from the UPS Gently lift the LCD module out Reinstall the right panel Step 2 Rotate the DB26 Connector of LCD Module Step 3 Connect the DB26 Cable Connect the DB26 cable from LCD module to the Remote Control Port on the front panel or rear panel as show...

Page 19: ...late the batteries Electrolyte fluid is harmful to the skin eyes and may be toxic CAUTION To avoid electric shock turn off and unplug the UPS from the wall receptacle before servicing the battery CAUTION Only use tools with insulated handles Do not lay tools or metal parts on top of the UPS or battery terminals Replacement Batteries Please refer to the front side of the Battery module for the mode...

Page 20: ...Bypass Step 4 Press ON OFF button to turn off UPS The UPS shutdown safely and it can perform routine maintenance or replacement now Turn the Manual Bypass Switch to Normal Step 1 Press ON OFF button to turn on UPS in Manual Bypass Step 2 Turn the Manual Bypass Switch to Normal Step 3 Put the Interlock Cover back Tighten the four screws and put the Interlock Cover back Step 4 Check the UPS auto tra...

Page 21: ...hort Circuit Protection UPS Output Cut off Immediately or Input Fuse Circuit Breaker Protection Battery Specifications 20 12V 7 2AH 20 12V 9 0AH Recharge Time Typically 4 hours 5 hours Sealed Maintenance Free Yes Hot Swappable Yes Status Indicators LCD Screen Multi Function LCD Readout that Supports Multi Language Interface 19 Types of Read Out 24 Types of Function Setting 3 Event Logs LED Indicat...

Page 22: ...ed Exchange line and neutral wires Missing ground wire Connect ground wire No ground wire Disable Wiring Fault alarm on LCD panel Line Abnormal Wrong utility power backed up during UPS auto restart Check whether voltage or frequency of utility power is out of range Output Short Output short circuit Your attached equipment may have problems please remove them and check again Over Temperature High a...