TROUBLE SHOOTING

 

13

 

Problem

 

Possible Cause 

Solution

 

Warning 

O/P Overload

 

Your  equipment  requires  more  power  than  the 
UPS  can  provide.  If  the  UPS  is  in  Line  Mode 
then it will transfer to Bypass Mode; if the UPS is 
in Battery Mode it will shutdown. 

Shut  off  non-essential  equipment.  If  this  solves 
the  overload  problem,  the  UPS  will  transfer  to 
normal operation. 

Load Over XXX% 

Your  equipment  requires  more  power  than  the 
setting  in  the  Power  Management  Software 
(PowerPanel

®

 

Business) will allow.

Shut off the non-essential equipment or increase 
the level in the Power Management Software. 

Battery Mode 

UPS is operating on battery power. 

Save  your  data  and  perform  a  controlled- 
shutdown. 

Battery Low 

UPS  is  operating  on  battery  power  and  will  be 
shutting down soon due to extremely low battery 
voltage. 

UPS  will  restart  automatically  when  acceptable 
utility power returns. 

BAT Disconnected 

Missing battery power. 

Check battery connector and battery breaker. 

Battery Failure 

UPS has failed a Battery Test. 

1. Check battery connector and battery breaker.
2. Contact  technical  support  to  replace  the

battery.

Replace Battery 

Battery  will  soon  need  to  be  replaced  due  to 
insufficient runtime. 

Contact technical support to replace the battery. 

EPO OFF 

Missing the EPO connection. 

Check the EPO connection. 

Wiring Fault 

Line and neutral wires are reversed. 

Exchange line and neutral wires. 

Missing ground wire. 

Connect ground wire. 

No ground wire. 

Disable Wiring Fault alarm on LCD panel. 

Line Abnormal 

Wrong utility power backed up during UPS auto- 
restart. 

Check  whether  voltage  or  frequency  of  utility 
power is out of range. 

Output Short 

Output short circuit. 

Your  attached  equipment  may  have  problems, 
please remove them and check again. 

Over Temperature 

High temperature sensor activates protection. 

Check the fan for operation and if the ventilation 
hole has been covered. 

Coldstart Lock 

UPS  is  locked  to  prevent  consuming  battery 
power during shipping. 

Plug into utility power for first-time operation. 

Autorestart Lock 

“Automatic  Restore”  is  disabled  in  Power 
Management Software (PowerPanel

®

 Business)

Press 

“ON/OFF“ button to turn on UPS. 

Replace Battery 

Battery  will  need  to  be  replaced  soon  due  to 
insufficient runtime. 

Install  new  batteries,  execute  battery  test,  and 
reset the replace battery date. 

Service Battery 
(Battery Expired) 

The Battery Replacement Date has reached the 
recommended 3 year maintenance period. 

1.

Perform  a  runtime  calibration  to  verify
battery capacity is sufficient and acceptable.

2. If batteries have been recently replaced, then

reset  the  Battery  Replacement  Date  using
PowerPanel®  

Business 

Edition-Agent

software, RMCARD interface (if installed)  or
through  the  LCD  control  panel  on  the  UPS
(see configuration menu on page 11).

Fault

 

Over Charge 

Battery is overcharged. 

1. Remove  battery  connector  and  check

charger voltage.

2. Contact CyberPower for repair.

Charger Failure 

Charger has failed. 

High O/P V 

Output voltage is too high. 

1. Shut down UPS and turn off input breaker.
2. Contact CyberPower for repair.

Low O/P V

 

Output voltage is too low. 

Bus Fault 

Internal DC bus voltage is too high or too low. 

Fan Error 

Internal Fan has failed. 

Cyber Power Systems

,

 Inc. 

www.c

yberpower

.com 

Entire contents copyright

©

 2017 Cyber Power Systems Inc., All rights reserved. Reproduction in whole or  in part

 

without permission is prohibited. PowerPanel

®

 Business Edition and PowerPanel

®

 Personal Edition are trademarks of

 

Cyber Power Systems Inc.

Summary of Contents for OL1000EXL

Page 1: ...User s Manual OL1000EXL OL1500EXL OL2000EXL OL3000EXL Cyber Power Systems Inc www cyberpower com K01 0000358 03 ...

Page 2: ... carry out installations CAUTION Do not unplug the unit from AC Power during operation as this will invalidate the protective ground insulation CAUTION To avoid electric shock turn off and unplug the unit before installing the input output power cord with a ground wire Connect the ground wire prior to connecting the line wires CAUTION Do not use an improper size power cord as it may cause damage t...

Page 3: ...lled indoor area free of conductive contaminants Do not install this UPS where excessive moisture or heat is present Please see specifications for acceptable temperature and humidity range CAUTION Never install a UPS or associated wiring or equipment during a lightning storm CAUTION Do not work alone under hazardous conditions CAUTION In case of the risk of electric shock do not remove the top cov...

Page 4: ...lephone fax machine or network device 5 Press the ON OFF switch to turn the UPS on The Power On indicator light will display when activated If an overload is detected an audible alarm will sound and the UPS will continuously emit two beeps per second For resetting the unit unplug some equipment from the outlets Make sure your equipment carries a load current within the unit s safe range refer to t...

Page 5: ...he power supply to equipment connected to NONCRITICAL outlets after a designated period of time 7 Serial Port Serial port provides communication between the UPS and the computer The UPS can control the computer s shutdown during a power outage through the connection while the computer can monitor the UPS and alter its various programmable parameters 8 USB port This is a connectivity port which all...

Page 6: ...Copyright 2017 Cyber Power Systems Inc BASIC OPERATION 5 OL1000EXL OL1500EXL OL2000EXL OL3000EXL ...

Page 7: ...Y Red Battery will soon need to be replaced due to insufficient runtime LCD SCREEN UPS STATUS LCD Screen UPS Status Description Line Mode UPS is operating in Line Mode Battery Mode UPS is operating in Battery Mode Bypass Mode UPS is operating in Bypass Mode Manual Bypass UPS is operating in Manual Bypass ECO Mode UPS is operating in ECO Economy Mode BUTTON OPERATION Button Operation Description ON...

Page 8: ...ays the Input Voltage I P Freq XX XHz Displays the Input Frequency O P Load XXX Displays the Output Load as a Percentage of Maximum load O P Amp X XA Displays the Output Current O P Watt XXXXXW Displays the Output Wattage O P VA XXXXXVA Displays the Output VA Load Energy XXXX XKWh Display UPS Load Energy Consumption BAT Volt XXX XV Displays the Battery Voltage BAT Cap XXX Displays the Estimated Pe...

Page 9: ... button to select the Language submenu 6 Press the and buttons to scroll to the language that you want to select You may be prompted to save the selection if so press the ENTER button to save the setting 7 Press the ESC button to cancel or return to previous LCD menu LCD SETTINGS CONFIGURATION There are 25 UPS settings that can be configured by the user 1 Press the ENTER button to activate the MAI...

Page 10: ...lish Español Spanish Français French Deutsch German English Generator Mode 2 Disable Enable Disable Communication Disable Enable Enable Dry Relay Set I P Power Fail Battery Low Summary Alarm UPS On Bypass UPS Fail I P Power Fail Converter Mode 3 Converter Off O P Freq 50Hz O P Freq 60Hz Converter OFF Screen Saver Disable 1 Minutes 5 Minutes 5 minutes Clear Event Log Activate None Button OFF LOCK D...

Page 11: ...attery Test portion of the LCD screen and the unit will perform a manual battery test GRAPHICAL LOAD BATTERY CAPACITY DISPLAY 1 Press the ESC button to return to UPS Status 2 Press the and buttons to scroll to the LOAD and BAT Capacity 3 Press the and buttons to scroll to the Charging or Discharging Capacity LOAD and BAT Capacity The LCD screen displays the Load and Battery capacity with a graphic...

Page 12: ...g the UPS from the wall receptacle before servicing the battery CAUTION Only use tools with insulated handles Do not lay tools or metal parts on top of the UPS or battery terminals Replacement Batteries Please refer to the front side of the UPS for the model number of the correct replacement batteries For battery procurement log onto www CPSww com or contact your local dealer Battery Disposal Batt...

Page 13: ...5 Load for 1 min 126 150 Load for 10 sec Battery Mode 105 130 Load for 10 sec 131 150 Load for 2 sec Short Circuit Protection UPS Output Cut off Immediately or Input Fuse Circuit Breaker Protection Battery Specifications 3 12V 7AH 3 12V 9AH 6 12V 7AH 6 12V 9AH Recharge Time Typically 5 hours Sealed Maintenance Free Yes Hot Swappable Yes Status Indicators LCD Screen Multi Function LCD Readout that ...

Page 14: ...s out of range Output Short Output short circuit Your attached equipment may have problems please remove them and check again Over Temperature High temperature sensor activates protection Check the fan for operation and if the ventilation hole has been covered Coldstart Lock UPS is locked to prevent consuming battery power during shipping Plug into utility power for first time operation Autorestar...

Reviews: