12
Use cable cross section and protective device specification
˖
˖
Model
OLS3S15KE(XL)/OLS3S20KE(XL)
Input Main1 L1,L2,L3
Min.conductor cross section
Max.conductor cross section
6mm²
10mm²
Input Main1 breaker
60A,250Vac
Input N, Main2
Min.conductor cross section
Max.conductor cross section
21mm²
25mm²
Input Main2 breaker
100A,250Vac
Input fuse
50A,690Vac
Output L,N,
Min.conductor cross section
Max.conductor cross section
21mm²
25mm²
External Battery Cabinet Positive
Pole(+), Negative pole(-),
Min.conductor cross section
Max.conductor cross section
21mm²
25mm²
Line input Backfeed protection
device
A 4-pole disconnection device with
100A/250Vac, less than 15s break time and
min. 1.4mm clearance will be used in final
installation for backfeed protection in line
input.
Main2 input Backfeed protection
device
A 2-pole disconnection device with
100A/250Vac, less than 15s break time
and min. 1.4mm clearance will be used in
final installation for backfeed protection in
line input.
Protective Earthing conductor
Max.25mm²(UL1015 6AWG)
(UL1015 8AWG)
(UL1015 6AWG)
(UL1015 6AWG)
(UL1015 6AWG)