Status Information Card 3
Configuring pins 2 and 5 (optional)
Possible settings:
Standard settings:
Replace battery
and
common electrical reference at 0V
.
Customer settings:
Replace battery
and
volt-free contacts
.
Customer setting:
Emergency Power Off
(EPO).
JP01
BATT.FAIL JP02
EPO JP03
GND JP04
Connected
Connected
Removed
Connected
Comments
• Pin 2 delivers the “replace battery” signal.
• Pin 5 is referenced to 0V.
JP01
BATT.FAIL JP02
EPO JP03
GND JP04
Connected
Connected
Removed
Removed
Comments
• Pin 2 delivers the “replace battery” signal.
• Pin 5 is volt-free.
JP01
BATT.FAIL JP02
EPO JP03
GND JP04
Removed
Removed
Connected
Connected
Comments
• Pins 2 and 5 receive the customer “Emergency Power Off” command: S1 wiring, max.
length 10m, see diagram below (pin 5 remains connected to 0V).
• Opening of external contact S1 immediately shuts the
Paragon UPS
off.
• The “Emergency Power Off” configuration only
works if pin 5 remains connected to 0V.
• Remote EPO switch wiring must be 10m maximum.
1
2
3
4
S1
5
9 8 7 6
External emergency
power off contact.