Status Information Card 3

Configuring pins 2 and 5 (optional)

Possible settings:

Standard settings:

 Replace battery

 and 

common electrical reference at 0V

.

Customer settings: 

Replace battery

 and 

volt-free contacts

.

Customer setting: 

Emergency Power Off

 (EPO).

JP01

BATT.FAIL JP02

EPO JP03

GND JP04

Connected

Connected

Removed

Connected

Comments

• Pin 2 delivers the “replace battery” signal.
• Pin 5 is referenced to 0V.

JP01

BATT.FAIL JP02

EPO JP03

GND JP04

Connected

Connected

Removed

Removed

Comments

• Pin 2 delivers the “replace battery” signal.
• Pin 5 is volt-free.

JP01

BATT.FAIL JP02

EPO JP03

GND JP04

Removed

Removed

Connected

Connected

Comments

• Pins 2 and 5 receive the customer “Emergency Power Off” command: S1 wiring, max. 

length 10m, see diagram below (pin 5 remains connected to 0V).

• Opening of external contact S1 immediately shuts the 

Paragon UPS

 off.

• The “Emergency Power Off” configuration only 

works if pin 5 remains connected to 0V.

• Remote EPO switch wiring must be 10m maximum.

1

2

3

4

S1

5

9 8 7 6

External emergency 
power off contact.