23
Web Interface
3-Phase Intelligent PDU User Guide
Power Protection
The configurable load threshold can be set to prevent an overload condition. Coldstart and system
configurations are also offered for different user needs. See
PDU Tab > Device Manager.
PDU Tab > Manager > Device
Item
Definition
HOST/GUEST#
Select the role of PDU (HOST or GUEST#) if PDUs are daisy
chained. Up to 3 GUEST PDUs can connect to 1 HOST PDU.
Load Configuration
Overload Threshold
Set the value for the total wattage on the PDU that will signal an
overload warning. Must be higher than
Near Overload Threshold
and equal to or lower than the PDU
Rating
Near Overload
Threshold
Set the value for the total wattage on the PDU that will signal a
near overload warning. Must be between
Overload Threshold
and
Low Load Threshold
.
Low Load Threshold
Set the value for the total wattage on the PDU that will signal a low
load warning. Must be lower than
Near Overload Threshold
.