Web Interface
3-Phase Intelligent PDU User Guide
Outlet Configuration Page
Item
Definition
Name
The name entered by the user to identify the selected outlet or multiple
outlet configuration.
Action Configuration
Power On/Off
Delay
*Instant: Turn on/off the outlet immediately.
*Delay: Delay time before turning on/off the outlet. Valid values
are within the range of 1 to 7,200 seconds.
*Never: Never turn on/off the outlet.
Reboot Duration
The length of time the outlet will remain off during a Reboot action. Valid
values are within the range of 5 to 60 seconds.
Load Configuration
Overload
Threshold
Set the value for individual outlet that will signal an overload warning in
Watts. Must be higher than
Near Overload Threshold
.
Near Overload
Threshold
Set the value for individual outlet that will signal a near overload
warning in Watts. Must be between
Overload Threshold
and
Low Load
Threshold
.