background image

 

The  LCD  display  indicates  a 
variety  of  UPS  operational 
conditions. 

All 

descriptions 

apply when the UPS is plugged 
into the AC outlet and turned on 
or when the UPS is on battery. 

10. Serial Port I 

Serial port allows connection and communication between the UPS and the 

computer.

 

 

11. Serial Port II   

Serial  Port  II  relays  information  to  equipment  that  can  utilize  a  contact 
closure UPS.   

12. SNMP/HTTP Network slot 

Remove  the  cover  panel  to  install  optional  RMCARD  that  allows  remote 
monitoring and control of your UPS on a network 

13. EPO (Emergency Power Off) Port: 

The EPO interface enables connection to an EPO master switch.

   

14. Ground Stud 

Use the Ground Stud to ground the UPS. 

15.External Battery Pack Connector: 

Provides a connection for additional CyberPower external battery packs for 
extended runtime. 

 
 
 
 

Smart App Sinewave Series 

PR750LCDRTXL2U/PR1000LCDRTXL2U/ 

PR1500LCDRTXL2Ua 

User’s Manual 

                                                                  K01-0000281-02 

 

 

 
This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. Please read 

and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, 
or operate. 

CAUTION!

    The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection. DO NOT plug the UPS into an 

outlet that is not grounded. If you need to de-energize this equipment, turn off and unplug the UPS.   

CAUTION!

   

DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT!

 CyberPower

 

Systems does not sell products for life support or 

medical applications. DO NOT use in any circumstance that would affect operation or safety of any life support equipment, with any medical 
applications, or patient care. 

CAUTION!

    The battery can energize hazardous live parts inside even when the AC input power is disconnected. 

CAUTION!   

For pluggable equipment, the socket-outlet shall be installed near the equipment and shall be easily accessible. 

CAUTION!

    To  prevent  the  risk  of  fire  or  electric  shock,  install  in  a  temperature  and  humidity  controlled  indoor  area,  free  of  conductive 

contaminants. (Please see specifications for acceptable temperature and humidity range). 

CAUTION!

    To reduce the risk of electric shock, do not remove the cover, except to service the battery. There are no serviceable parts inside, 

except for the battery. 

CAUTION!

    To  avoid  electrical  shock,  turn  off  the  unit  and  unplug  it  from  the  AC  power  source  before  servicing  the  battery  or  installing  a 

computer component. 

CAUTION!

   

DO NOT USE WITH OR NEAR AQUARIUMS!

 To reduce the risk of fire, do not use with or near aquariums. Condensation from the 

aquarium can come in contact with metal electrical contacts and cause the machine to short out. 

CAUTION!   

For  model 

PR750LCDRTXL2U,  PR1000LCDRTXL2U  and  PR1500LCDRTXL2Ua

  use  in  a  computer  room  as  defined  in  the 

standard for the Protection of Electronic Computer/Data Processing Equipment, ANSI/NFPA 75. 
 
 
 

UNPACKING 

Inspect the UPS upon receipt. The box should contain the following. 

(1)  UPS  Unit;  (1)  User's  Manual  for  UPS;  (2)  Rack  Mount  Brackets;  (1)  Metal  Stand  Plate;  (1)  Emergency  Power  Off  Cable  (gray);  (1) 
PowerPanel

®

 Business Edition Software CD; (2) Serial Interface Cable (DB-9); (1) USB A+B Type Cable; (1) Warranty Registration Card; (4) 

Rubber Buffer. 
 

OVERVIEW 

The

  PR750LCDRTXL2U/PR1000LCDRTXL2U/PR1500LCDRTXL2Ua 

provides  battery  backup,  automatic 

voltage regulation (AVR), and optimal performance of computers and other network equipment by ensuring 

consistent sinewave power. The 

PR750LCDRTXL2U/PR1000LCDRTXL2U/PR1500LCDRTXL2Ua 

features 

2060  Joules  of  surge  protection,  and  provides  battery  backup  during  power  outages.  The

 

PR750LCDRTXL2U/PR1000LCDRTXL2U/PR1500LCDRTXL2Ua 

ensures  consistent  power  to  your 

computer  system  and  its  included  software  will  automatically  save  your  open  files  and  shutdown  your 
computer system during a utility power loss.

 

 

AUTOMATIC VOLTAGE REGULATOR(AVR)

 

The 

PR750LCDRTXL2U/PR1000LCDRTXL2U/PR1500LCDRTXL2Ua 

stabilizes  inconsistent  utility  power.  The  incoming  utility  power may  be 

damaging to important data and hardware, but with Automatic Voltage Regulation, the computer will not experience damaging voltage levels. An 
Automatic Voltage Regulator automatically increases low or decreases high voltage to a consistent, computer safe 110V/120V. The unit powerful 
sealed lead-acid batteries will provide power only if the incoming voltage drops below 80V or increases above 150V. 

 

SYSTEM BLOCK DIAGRAM 

 
 

 
 

 
 
 

 
 

 
 

 

 

HARDWARE INSTALLATION GUIDE 

1. Your new UPS may be used immediately upon receipt. However, recharging the battery for at least four hours 
is  recommended  to  ensure  that  the  battery's  maximum charge  capacity  is  achieved.  Charge  loss may  occur 

during shipping and storage. To recharge the battery, simply leave the unit plugged into an AC outlet. The unit 
will charge in both the on and off position.   
2. If you plan to use the included software, connect either the serial cable or the USB cable to the corresponding 

port  on  the  UPS  and  the  computer.  Note:  if  the  USB  port  is  used  the  serial  port  will  be  disabled.  To  control 
multiple computers install PowerPanel

®

 Business Edition Agent on the computer connected with the USB cable 

and PowerPanel

®

 Business Edition Slave on the remaining computers. 

3.  With  the  UPS  unit  off  and  unplugged,  connect  your  computer,  monitor,  and  any  externally  powered  data 

storage device (Hard drive, Tape drive, etc.) into the battery power supplied outlets. DO NOT plug a laser printer, 
copier, space heater, vacuum, paper shredder or other large electrical device into the UPS. The power demands 
of these devices will overload and possibly damage the unit.   

4.  Plug  the  UPS  into  a  2  pole,  3  wire  grounded  receptacle  (wall  outlet).  Make  sure  the  wall  branch  outlet  is 
protected  by  a  fuse  or  circuit  breaker  and  does  not  service  equipment with  large  electrical  demands  (e.g.  air 

conditioner, refrigerator, copier, etc.). Avoid using extension cords.   
5.  Depress the  power switch  to  turn  the  unit  on.  The  Power  On  indicator light will  illuminate.  If  an  overload  is 
detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and 

unplug at least one piece of equipment from the battery power supplied outlets. Wait 10 seconds. Make sure the 
circuit breaker is depressed and then turn the UPS on. 

6. Your UPS is equipped with an auto-charge feature. When the UPS is plugged into an AC outlet, the battery will 
automatically recharge. 

7. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times. 
8.  To  store  your  UPS  for  an  extended  period,  cover  it  and  store with  the  battery  fully  charged.  Recharge  the 
battery every three months to ensure battery life. 

9.  Professional  Rack  Mount  UPS  provide  one  serial  port,  one  dry  contact  port,  and  one  USB  port  to  allow 
communication  between  the  UPS  and  computers  or  equipment.  The  dry  contact  port  (Serial  Port  II)  signals 

information for equipment that can utilize a dry contact UPS. The primary computer, with PowerPanel

®

 Business 

Edition installed,  connected  to  Serial Port  I  or  the  USB  port is  the computer  that  you  use to  control  the  UPS. 
When there is a power failure, the primary computer which connects to Serial Port I or the USB port will start to 

shutdown after a user controlled delay. PowerPanel

®

 Business Edition Agent software will save and close any 

open files prior to shutting the system down and signal any configured slaves to shutdown. 

10. EPO (Emergency Power Off) Port: 
The  feature  is  used with  EPO  controllers.  Use  the  provided  gray  cable  to  connect  to  an EPO  contact switch. 

Follow the appropriate circuit diagram below to wire the cable to match your EPO configuration. EPO function is 
provided in the UPS. EPO remote switch which is a Push-Back button installed computer room outside by a EPO 
cable, and not connected any other equipment. 

 
 

 
 
 

 
 

 
 

 
 
 

 
 

 
 
 

 
 

 

FRONT / REAR PANEL DESCRIPTION 

1

.

 Power Switch

 

Master on/off switch for equipment connected to the UPS. 

2. Power On Indicator 

Indicates the power is on.   

3. LCD Module Display 

LCD shows all the UPS information with icons and messages.   

4

.

 LCD Display Toggle Button 

The button can be used to toggle between different data displays 
on the LCD.   

5

Battery Backup Protected Outlets 

Provides eight battery powered, surge protected and AVR outlets 

for  connected  equipment  and  ensures  temporary  uninterrupted 
operation of connected equipment during a power failure.   

Critical /Non-critical   

When the UPS is overloaded, the circuit breakers will be tripped 
to  interrupt  the  power  supply  to  the uncritical  outlets  while 

continuing  to  supply  the  critical  outlets.  As  well,  as  the  battery 
capacity depletes under the threshold value, the uncritical outlets 

will

 

be  shut  down  and  provide  energy  for  critical  outlets.  The 

threshold  can  be  determined  and  set  by  users.  Non-critical 
outlets can  also  be  turned  on/off manually  through  the software 

package

 

provided. 

6

.

 Input Power Cord 

Heavy-duty, extra long power cord.

 

7

.

 Input Circuit Breaker 

Resettable  circuit  breakers  provide  Input  optimal  overload 

Protection. 

8

USB port

USB communication port for management software. 

9. Site Wire Fault Indicator

 

This  LED  will  illuminate  to  warn  the  user  that  a  wiring  problem 
exists within the AC receptacle, such as a bad ground or reversed 
wiring.  If  illuminated,  disconnect  all  equipment  and  contact  an 

electrician to ensure outlet is properly wired. 
 

 
 
 

 

Contact  your  dealer,  or  email  tech@cpsww.com.  Refer  to  replacement  battery  pack  number 

RB1270X4F

 

for 

PR750LCDRTXL2U 

/PR1000LCDRTXL2U/PR1500LCDRTXL2Ua.

 

For model 

PR750LCDRTXL2U, PR1000LCDRTXL2U and PR1500LCDRTXL2Ua 

can support model 

BP48V45ART2U

 for external battery pack.

   

Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery. Service the battery under the supervision of personnel 
knowledgeable of batteries and their precautions

. Servicing the battery should only be performed by trained personnel.

 

Replacement of batteries located in an 

OPERATOR ACCESS AREA.

 

CAUTION!

    W hen  replacing  batteries,  replace  with  the  same  number  of  the  following  battery:  BP7.2-12FR(BB)  for 

PR750LCDRTXL2U/ 

PR1000LCDRTXL2U/PR1500LCDRTXL2Ua. 

CAUTION!   

Risk  of  energy  hazard,  12V,  maximum  7.2  Ampere-hour  battery  (BP7.2-12FR).  Before  replacing  batteries,  remove  conductive 

jewelry such as chains, wrist watches, and rings. High energy through conductive materials could cause severe burns. 

CAUTION!

    Risk of battery explosion, if battery is replaced by an incorrect type. Dispose of used battery according to the instructions. 

CAUTION!

    To  reduce  the  risk  of  fire,  connect  only  to  a  circuit  provided  with  20  amperes maximum  branch  circuit  overcurrent  protection  in 

accordance with the National Electric Code, ANSI/NFPA 70. 

CAUTION!

    Use only the specified CyberPower replacement battery, or battery pack. See your dealer for details. 

CAUTION!   

The  battery  may  present  a  risk  of  electrical  shock.  Do  not  dispose  of  batteries  in  a  fire,  as  they  may  explode.  Follow  all  local 

ordinances regarding proper disposal of batteries. 

CAUTION!

    Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes and may be toxic. 

CAUTION!   

A battery may present a high risk of short circuit current and electrical shock. 

 
Take the following precautions before replacing the battery

1. Remove all watches, rings or other metal objects. 
2. Only use tools with insulated handles. 
3. Do not lay tools or metal parts on top of battery or any terminals. 

4. Wear rubber gloves and boots. 
5.  Determine  if  the  battery  is inadvertently  grounded.  If  inadvertently  grounded,  remove  source  of  ground. 

CONTACT  WITH  A  GROUNDED 

BATTERY CAN RESULT IN ELECTRICAL SHOCK! 

The likelihood of such shock will be reduced if such grounds are removed during installation 

and maintenance (applicable to a UPS and a remote battery supply not having a grounded circuit). 

 
BATTERY REPLACMENT PROCEDURE: 

 

 

 

 
 
 

 
.   

 
 

 
 

 

 

 

 
 

 

 
 

 
 

 
 
 

 
 

 
 
 

INPUT voltage  meter:

  This meter measures  the  AC  voltage  that  the  UPS system  is  receiving  from  the 

utility wall outlet. The INPUT voltage readout can be used as a diagnostic tool to identify poor-quality input 

power. The AVR in this UPS continuously conditions the power to a stable 110/120V output to connected 
equipment. In the event of a complete power loss, severe brownout, or over voltage, the UPS relies on its 

internal battery back up to supply a consistent 110/120V output.

 

OUTPUT  voltage  meter:

  This  meter  measures  in  real  time,  the  AC  voltage  that  the  UPS  system  is 

providing to the computer, such as normal line mode, AVR mode and battery back up mode. 

Note: The OUTPUT voltage readout displays the status of the battery back up outlets. 

ESTIMATE RUN TIME:

  This displays the run time estimate of the UPS with the current battery capacity 

and load. 

NORMAL icon:

 This icon appears when the UPS is working under normal conditions. 

BATTERY icon:

 During a severe brownout or blackout, this icon appears and an alarm sounds (two short 

beeps followed by a pause) to indicate the UPS is operating from its Internal batteries. During an extended 
brownout  or  blackout  that  drains  the  battery,  a  continuous  alarm will  sound  (and  the  BATT.  CAPACITY 

readout will show a single shaded segment, equaling 20% battery capacity remaining) indicating the UPS 
batteries are nearly out of power. If this occurs, it is recommended that you save your files and manually 

power down your equipment immediately.   

Automatic  Voltage  Regulation  (AVR)  icon

:  This  icon  appears  whenever  your  UPS  is  automatically 

correcting low AC input line voltage without using battery power. This is a normal, automatic operation of your UPS, and no action is required. 

SILENT MODE icon:

  This icon appears whenever the UPS is in silent mode. The buzzer does not beep during silent mode until the battery 

reaches low capacity. 

OVER LOAD icon:

 This icon appears and an alarm sounds to indicate the battery-supplied outlets are overloaded. To clear the overload, unplug 

some of your equipment from the battery-supplied outlets until the icon turns off and the alarm stops. 

FAULT icon:

 

This icon appears if there is a problem with your UPS.   

BATT.

 

CAPACITY meter: 

This meter displays the approximate charge level (in 20% increments) of the UPS's internal battery. During a blackout 

or severe brownout the UPS switches to battery back up power the BATT. CAPACITY icon appears and the charge level decreases. 

LOAD CAPACITY:

 This meter displays the approximate output load level (in 20% increments) of the UPS’s battery outlets. 

IMPORTANT SAFETY WARNINGS

 

INSTALLING YOUR UPS SYSTEM 

LCD STATUS DEFINITION 

BATTERY REPLACEMENT 

BASIC OPERATION

 

When  you  first  receive  the 
unit,  plug  in  the  unit  to  fully 

charge the battery. 

Unplug the unit and turn Power 
Off  when  first  connecting  your 
computer and peripherals. 

1. Remove two screws and front 
panel on the right side.

 

2. Remove the four retaining screws of 
the cable protection cover then remove 
the cover. 

3. unplug cable connectors. 

4. Pull out the old battery pack and replace new one. 

Reassemble the retaining screws, covers, black and 
red cable, and front panel in the reverse sequence 

of the above steps. Recharge the unit for 4-8 hours 
to ensure maximum UPS battery runtime. 

Primary Computer-

 

Install PowerPanel

 

®

 

 

Business Edition

Install PowerPanel

®

 

Business Edition 
software on the primary 
computer connected to 
the UPS with either a 
serial cable or a USB 
cable.

The equipment can 
read information 
from dry contact

 

*Dry connect is controlled by the PowerPanel

®

 Software. 

Please go to 

www.cyberpowersystems.com

 for free download. 

 

*Note:Both USB and Serial can not be used simultaneously.

 