Smart Tower UPS 10-30KVA User Manual
Chapter 2 Installation Guidance
3
2.2.2 Battery Room
The batteries will generate a small amount of hydrogen and oxygen at the end of charging, so keep
the batteries installation environment adequate fresh air ventilation must meet EN50272-2001
requirements.
The ambient temperature of the batteries should be stable. Environment temperature is the main
factor influent batteries capacity and life.
The batteries standard operation temperature is 20°C. Above this temperature, it will reduce the
battery life, and below this temperature it will reduce the battery capacity.
If the average operation temperature of battery is increased from 20ºC to 30ºC, then the life of the
battery will be reduced by 50%. If the operating temperature of the battery is above 40ºC, then the battery
life will be decreased in exponent rate.
In normal situation, the battery allowing temperature should be at 15°C to 25°C. Keep batteries far
away from heat and air vents.
UPS use external batteries, and the battery protection device (a DC circuit breaker) must be
mounted close to batteries as possible. Between it with batteries, use the shortest power cables
connection distance.
2.2.3 Storage
If there is no need to install the UPS immediately, must be kept the UPS inside a room so as to
protect it against too wet or too hot environment.
The battery needs to be stored in a dry and cool place with good ventilation. The most appropriate
storage temperature is 20 ºC ~ 25ºC.
2.3 Disassembly, Initial Checking and Positioning
When the product is delivered to the user after the first inspection, packaging, determine the intact;
and then open the package, check the equipment integrity; if damaged, please immediately notify the
carrier.
2.3.1 System Disassembly
Open the wooden case first, and then take out the foam pay attention not to scratch the UPS
Fig 2-1 UPS Packing Diagram
Tip: After disassembly, as shown in Figure 2-1, remove the bolts that connect to the UPS
cabinet and wooden Cashion, then lift the UPS cabinet to the installation position. The
dismantlement should be careful so as not to scratch the UPS.