5. MEASURING PROCEDURES
5-1 1
Φ
2W ( one phase by two wires ) measurement
A : Diagram
SCREEN 1 ( 5-1 )
B : Operation Instructions:
B-1 : Power on the instrument by pressing POWER
KEY, and then press 1
Φ
3
Φ
KEY to select the 1
Φ
2W
system, the selected name of system will be
appeared on bottom left display of screen 2.
B-2 : Connect the line voltage L1, Vn ( Neutral ) to
V1 and N terminals of the instrument.
B-3: Place the conductor of CP-1200 (A1)to A1 as
screen 1.
B-4: Connect the output of clamp meter " CP-1200(A1) "
to A1 terminal of the instrument.
B-5: The related measuring factors will be appeared on
display, about the instruction of factor please refer
appendix 1 ( 5-11, page 49 ).
35