Circuit Breakers
109
PM10-L30A
PM10-L30A
The PM10-L30A has two 15-amp circuit breakers. The first circuit breaker
controls outlets 1 through 5 and the power supply to the logic board; the
second circuit breaker controls outlets 6 through 10. If the total current flow to
outlets 6 through 10 exceeds 15 amps due to equipment connected to these
outlets, then the second circuit breaker will trip causing outlets 6 through 10 to
shut down. This does not affect outlets 1 through 5, which are controlled by
the first circuit breaker.
If, however, current overload causes the first circuit breaker to trip, then the
entire power unit shuts down because the power supply is also tied to the first
circuit breaker.
Refer to Table C-20, “Circuit Breaker Trip Time,” on page 114 to determine
the time it takes for the circuit breaker to trip based on the amount of current
overload.
Figure C-1:
PM10-L30A Circuit Breakers