1-10
AspectFT-Matrix MAX Area Controller Installation Guide (1/05/2015)
1.5 P
RODUCT
S
PECIFICATIONS
1.5.1 EIA-485 C
ONNECTIONS
.
Connection Type:
3 position
.
Termination Count:
model dependent, up to 2 connections
.
Serial:
EIA-485
.
Baud Rates Supported:
9.6kbps, 19.2kbps, 38.4kbps, 57.6kbps, 76.8kbps, 115.2kbps
.
Data isolation:
GMR Data Isolated
.
Termination:
249 Ohm, switch selectable
.
Biasing:
3.32k, switch selectable
.
LED:
indication for TXD, RXD, Byte-Error, Parity-Error
.
Protocol:
license enforced, driver selectable
.
Network Load:
license enforced, up to 64 devices per port, license restrictions apply
1.5.2 E
THERNET
C
ONNECTION
.
Termination Count:
1 connection
.
Connection Type:
RJ-45, female
.
Speed:
10/100Mb auto-sensing
1.5.3 P
RODUCT
S
ETUP
AND
C
ONFIGURATION
.
Software
: AspectStudio with USB Copy Protection Key and License File
.
Browser:
Windows Internet Explorer v7.0 or later, Mozilla Firefox v3.0 or later, Apple Safari v3.2 or
later, Google Chrome v1.0 or later
1.5.4 CPU
.
Processor:
ARM Cortex-A8 1 Ghz
.
Memory:
512MB RAM, 2 GB Flash
1.5.5 P
OWER
R
EQUIREMENTS
.
Connection:
2 position
.
Power Source:
24 VAC, 50/60Hz, 2.7A max
1.5.6 O
PERATING
C
ONDITIONS
.
Temperature:
32-104
o
F (0- 40
o
C) ambient
.
Humidity:
0-80%, non-condensing
.
Altitude:
-2000 to + 10,000 ft. (-650 to + 3500m)
1.5.7 A
GENCY
A
PPROVALS
.
CE Approved
.
FCC, Class A Computing Device; Part 15
.
UL listed 916, Management Equipment, Energy (PAZX)