1-4

AspectFT-Matrix MAX Area Controller Installation Guide (1/05/2015)

Figure 1-2 AspectFT-Matrix MAX enclosure

Figure 1-3 Enclosure cover removal

Summary of Contents for American Auto-Matrix Aspect Matrix MAX

Page 1: ...Matrix MAX Hardware Installation Guide...

Page 2: ...ctors Drill for mounting the product onto a wall Wire strippers for terminating EIA 485 connections 1 1 2 SAFETY PRECAUTIONS NOTE All equipment must be installed in accordance with NEC and local codes...

Page 3: ...ject Do not handle the printed circuit board PCB without proper protection against static discharge Users should handle PCB components while wearing a ground bracelet or strap connected to Earth groun...

Page 4: ...cation that allows clearance for ease of wiring and service Use the two keyhole style screw holes located on the back of the enclosure for assistance with mounting The product is capable of being moun...

Page 5: ...1 4 AspectFT Matrix MAX Area Controller Installation Guide 1 05 2015 Figure 1 2 AspectFT Matrix MAX enclosure Figure 1 3 Enclosure cover removal...

Page 6: ...out of the product The device includes connection ports for Main Power EIA 485 network connectivity and Ethernet connectivity Depending on the model of Matrix MAX Area Controller you have purchased yo...

Page 7: ...nds using 18AWG cable for power wiring 24VAC Output J1 PWR PWR Figure 1 5 Connecting Power to Matrix MAX Area Controller WARNING Do not share the power source for AspectFT Matrix MAX MAX Area Controll...

Page 8: ...sers communicate with the device for product setup as well as for building automation routines and applications The Ethernet network interface is located on the single board computer card The on board...

Page 9: ...apped or starred 1 4 2 1 CONNECTING EIA 485 NETWORKS Connect the serial network to the determined EIA 485 port Be sure to maintain network polarity at all times Failure to do so can result in loss of...

Page 10: ...will flash upon the event a parity error occurs on the network A parity error is caused by a mismatch between the calculated checksum and value received with the packet The most common reason for a pa...

Page 11: ...ns apply 1 5 2 ETHERNET CONNECTION Termination Count 1 connection Connection Type RJ 45 female Speed 10 100Mb auto sensing 1 5 3 PRODUCT SETUP AND CONFIGURATION Software AspectStudio with USB Copy Pro...

Page 12: ...ce marks or logos contained herein are the property of their respective owners and are only used to describe the product s being listed in this document Every effort has been made to properly capitali...