32/36
CPS-M1-MSE
English
99.828.70 1.2/07/22
Designation
Connection
Description
Digital output
Output inverted
The output issues the status of the link inverted.
Functionality selection
SHEV link: Alarm / Alarm Reset / Alarm Pulse / Fault / Not Closed
Ventilation link: Not Closed / LT Open forwarding / LT Closed forwarding
Supplied with emergency power The output is also triggered in the event of a mains outage. An additional 0.072 Ah
is to be taken into consideration in the battery capacity calculation. Furthermore, the
current consumption of the connected peripherals is to be taken into consideration.
Functionality
SHEV link: Alarm / Alarm Pulse / Alarm Reset and RT Closed / Alarm and Alarm
Reset with RT Closed / Fault
Ventilation link: LT Open / LT Closed / LT Stop / LT Open pulse / LT Closed pulse /
LT Open and Closed pulse / LT Closed and Open pulse / LT Open pulse and Closed
pulse
Digital input
Inverted
The status of the input is forwarded to the link inverted.
Active negative
The input is activated if switched to -.
Active positive
The input is activated if switched to P+ or N+.
Group
Actuator type
The group is used for triggering ACB drives or pole-changing drives. The type used
must be selected for each group.
Alarm re-clocking
The group will be triggered every 2 minutes for 30 minutes in the event of an alarm.
This function is a requirement of VdS 2581.
Open – running time limit
The group moves in the OPEN direction for the set time if the ventilation button is
switched to the OPEN direction.
Open – retriggering
The group once more moves in the OPEN direction for the set time if the ventilation
button is again switched to the OPEN direction.
For alarm Closed
The group moves in the CLOSED direction if the SHEV link to which the group is
assigned is triggered.
For communication fault Closed
The group moves in the CLOSED direction if a communication fault occurs within a
link to which the group is assigned.
Group fault triggers alarm
In the event of a group fault (e.g. a monitoring cable is interrupted or an addressed
ACB drive is not available), the SHEV link to which the group is assigned is trig
-
gered.
Ventilation time active
The group automatically moves in the CLOSED direction upon expiry of the set
ventilation time.
Mains outage CLOSED
The group automatically moves in the CLOSED direction in the event of a mains
outage. Only the control panel groups move in the CLOSED direction in the event
of a mains outage. Groups in the same link belonging to another CPS-M are not
affected by this.
Storage operation OPEN
The group moves in the OPEN direction when a ventilation button of the ventilation
link is pressed once.
Storage operation CLOSED
The group moves in the CLOSED direction when a ventilation button of the ventila
-
tion link is pressed once.
Stop-hold function
The supply cables MOT.A x and MOT.B x are short-circuited in the Stop status. A
short circuit between these two cables can no longer be recognized as being a fault
in this status.
Button operation OPEN
The group moves in the OPEN direction for as long as the ventilation button of the
ventilation link is pressed.
Button operation CLOSED
The group moves in the CLOSED direction for as long as a ventilation button of the
ventilation link is pressed.
Line
Line fault triggers alarm
In the event of a line fault (e.g. an interrupted cable), the SHEV link to which the line is
assigned is triggered.
Smoke detector can only be
locally reset
A smoke detector alarm cannot be reset by pressing the “SHEV CLOSED” button on
the SHEV button panel. It is possible to reset the alarm via the touch panel.
Two-detector dependency
(Only with SD-O 371/FO 1362) Alarm will be triggered only, if at least two smoke
detectors of one line respond. False alarm of one smoke detector will be prevent
-
ed. Two smoke detectors in one room must be always installed. If only one smoke
detector is connected to one line, switch must be on OFF!
Isolated output
Output inverted
The output issues the status of the link inverted.
Functionality selection
SHEV link: Alarm / Alarm Reset / Alarm Pulse / Fault / Not Closed
Ventilation link: Not Closed / LT Open forwarding / LT Closed forwarding
Supplied with emergency power
(monostable, CM)
The output is also triggered in the event of a mains outage. This must be taken into
consideration in the battery capacity calculation.
Failsafe in case of power failure
(bistable, BRM)
With this the state of the potential-free contact can be defined, which is to be taken
in case of a failure of the mains and battery supply.
If the "None" configuration is selected, the last status is retained.
Event log
internal
All status changes of the CPS-M are written with time stamp in an event log. These
can be read out via the SCS software.
Description of the software functions