5/36
CPS-M1-MSE
English
99.828.70 1.2/07/22
Control module – CM-BT1-D4-P2
Control module – CM-B-1-D4-P2
• Central control element of the control panel (segment coupler)
• One CM controller module is required for each CPS-M
• Each CM controller module can manage up to 29 addition-
al modules (PSM, AM, TMA)
• AdComNet interfaces for implementing decentralised sys-
tems in combination with other AdComNet control panels
•
1000 SCS links and 100 connectors possible
•
USB interface for configuring the system and the con
-
nected drives (only ACB), and for firmware updates of the
control panel
• Integrated LEDs to indicate operation (green), fault
(yellow), alarm (red) and AdComNet operation
• Status displays for all modules of the respective CPS-M
as well as emergency operation of the individual lines and
groups using the 3.5" TFT touch panel
•
Three user-programmable digital inputs for connecting
buttons, switches, external controls etc.
•
Two user-programmable, isolated change-over contacts,
for example, for fault and alarm notifications
• Integrated event memory for system analysis and traceability
• Connection using removable spring-type terminals
•
Conductor cross-sections max. 1.5 mm² flexible
• Dimensions WxHxD: 26x130x125 mm
•
Installation on a 35 mm top hat rail in combination with a
basic module socket
• Central control element of the control panel (segment coupler)
• One CM controller module is required for each CPS-M
• Each CM controller module can manage up to 29 addition-
al modules (PSM, AM, TMA)
•
30 SCS links and 10 connectors possible
•
USB interface for configuring the system and the con
-
nected drives (only ACB), and for firmware updates of the
control panel
• Integrated LEDs to indicate operation (green), fault
(yellow), alarm (red) and AdComNet operation
• Status displays for all modules of the respective CPS-M
as well as emergency operation of the individual lines and
groups using the 3.5" TFT touch panel
•
Three user-programmable digital inputs for connecting
buttons, switches, external controls etc.
•
Two user-programmable, isolated change-over contacts,
for example, for fault and alarm notifications
• Integrated event memory for system analysis and traceability
• Connection using removable spring-type terminals
•
Conductor cross-sections max. 1.5 mm² flexible
• Dimensions WxHxD: 26x130x125 mm
•
Installation on a 35 mm top hat rail in combination with a
basic module socket
Supply module – PSM-1-24-040
•
Power supply of the control panel system
• Max. 40 A load current for each supply module
depending on the power supply unit
• If a load current of more than 40 A is required, another
PSM (including supply module socket) can be used.
•
The PSM always provides power to the actuator and
trigger modules used to the right of it
•
Automatic toggling between mains supply and battery
supply in case of a mains outage
• Max. battery capacity 26 Ah (battery type 6)
• 72 hours of emergency supply time
• Integrated protection against excessive discharge
•
Temperature-controlled charging voltage with external
temperature sensor
•
Integrated LED to indicate a fault (yellow)
•
Two connections for peripherals that are and are not
supplied with emergency power
• Connection using removable spring-type terminals
•
Conductor cross-sections max. 2.5 mm² flexible or for
supply and battery 6 mm² flexible
• Dimensions WxHxD: 26x130x125 mm
•
Installation on a 35 mm top hat rail in combination with
a basic module socket or for more than one power
supply unit with a supply module socket
Actuator module – AM-1-2-10-24-D6-D2
Actuator module – AM-B-1-2-10-24-D4-D2
•
Module for connecting 24 V DC actuators
•
2 independent groups for connecting drives, each with
a total maximum current of 10 A
•
The cable is monitored for breaks and short circuits
via the terminal module EM-47K
• Each group is electronically protected against
overload
• 4 user-programmable digital inputs (e.g. ventilation
button)
•
2 user-programmable digital outputs (e.g. NOT
CLOSED signal)
• 2 integrated ACB interfaces for reading out and
configuring the connected ACB drives
•
Can be used with 24 V DC pole-changing drives, ACB
drives, spring-return motors and magnets
•
Virtual groups in connection with ACB drives possible
•
Adjustable ventilation time and opening width for
everyday ventilation
•
Integrated LEDs to indicate a fault (yellow) and alarm
(red)
• Connection using removable spring-type terminals
• Conductor cross-sections max. 2.5 mm² Flexible
• Dimensions WxHxD: 26x130x125 mm
•
Installation on a 35 mm top hat rail in combination with
an expansion module socket
•
Module for connecting 24 V DC actuators
•
2 independent groups for connecting drives, each with
a total maximum current of 10 A
•
The cable is monitored for breaks and short circuits
via the terminal module EM-47K
• Each group is electronically protected against
overload
• 4 user-programmable digital inputs (e.g. ventilation
button)
•
2 user-programmable digital outputs (e.g. NOT
CLOSED signal)
•
Can be used with 24 V DC pole-changing drives
•
Integrated LEDs to indicate a fault (yellow) and alarm
(red)
• Connection using removable spring-type terminals
• Conductor cross-sections max. 2.5 mm² Flexible
• Dimensions WxHxD: 26x130x125 mm
•
Installation on a 35 mm top hat rail in combination with
an expansion module socket
Trigger module – TMA-1-D4-D12
• Module for connecting trigger peripheral devices
•
Two independent lines for connecting a max. of 10
SHEV buttons and 30 fire detectors per line (only
detectors approved by D+H may be used)
• Cables are monitored by the EM-L01 terminal module
•
The SCS software can be used to configure the lines
also as user-programmable digital inputs and outputs
•
Integrated LEDs to indicate a fault (yellow) and alarm
(red)
• Connection using removable spring-type terminals
•
Conductor cross-sections max. 1.5 mm² flexible
• Dimensions WxHxD: 26x130x125 mm
•
Installation on a 35 mm top hat rail in combination with
an expansion module socket