English
99.828.70 1.2/07/22
Connection – AM 230
Ventilation button
Connection – NSV 401 control and vent button to AM 230
No.
Name
Description
X1.1 N
Neutral conductor input
X1.2 L
Phase 230 V input
X2.1 N
Neutral conductor output
X2.2 L-OPEN
Phase 230 V OPEN direction output
X2.3 L-CLOSE
Phase 230 V CLOSE direction output
X2.4 E
Monitoring wire
X4.5
-
Reference potential (do not connect to P-)
X4.4
ACB +
Supply of the ACB interface
X4.3
ACB.A
ACB interface of drive group
X4.2
ACB.B
X4.1
SGI
Position transmitter for drive group
(not yet implemented)
X5.4 DO 1.1
Freely configurable digital output 1.1, max. 50 mA /
NOT CLOSED signal LT
X5.3 -
Reference potential (do not connect to P-)
X5.2 DI 1.1
Freely configurable digital input 1.1,
0 to 28 V, active minus or plus / OPEN LT
X5.1 DI 1.2
Freely configurable digital input 1.2,
0 to 28 V, active minus or plus / CLOSE LT
X6.4 -
Reference potential (do not connect to P-)
X6.3 FES
Fault NSV
X6.2 -
Reference potential (do not connect to P-)
X6.1 SES
Start NSV
, max. 50 mA
Please Note:
If the AM 230 is used as a pure ventilation group, the line monitoring
can be switched off. In this case, no EM 230 end module is required.
For description
and connection
of NSV 401,
see page 24
Note:
All AM 230 connected to an NSV 401
must also be connected to the same
PSM module.
(See page 27)