27/36
CPS-M1-MSE
X1
X6
X2
X5
X4
X3
English
99.828.70 1.2/07/22
Connection – TMA
No.
Name
Description (as digital inputs/outputs)
X1.1 DO 2.3
Freely configurable digital output 2.3, max. 50 mA
X1.2 DO 2.2
Freely configurable digital output 2.2, max. 50 mA
X1.3 -
Reference potential (do not connect to P-)
X1.4 DO 1.3 (S)
Freely configurable digital output 1.3, max. 50 mA
X1.5 DO 1.2 (A)
Freely configurable digital output 1.2, max. 50 mA
X2.1 DO 1.1 (K)
Freely configurable digital output 1.1, max. 50 mA
X2.2 DI 1.1 (Z)
Freely configurable digital input 1.1, 0 to 28 V, active minus or plus
X2.3 -
Reference potential (do not connect to P-)
X2.4
LINIE 1 (T)
No function
X2.5 FE
Functional earth
X3.1
DO 2.1
Freely configurable digital output 2.1, max. 50 mA
X3.2
DI 2.1
Freely configurable digital input 2.1, 0 to 28 V, active minus or plus
X3.3
-
Reference potential (do not connect to P-)
X3.4
LINIE 2 (R) No function
X3.5
FE
Functional earth
X4.5
FE
Functional earth
X4.4
LINIE 3 (R) No function
X4.3
-
Reference potential (do not connect to P-)
X4.2
DI 3.1
Freely configurable digital input 3.1, 0 to 28 V, active minus or plus
X4.1
DO 3.1
Freely configurable digital output 3.1, max. 50 mA
X5.5 FE
Functional earth
X5.4
LINIE 4 (T)
No function
X5.3 -
Reference potential (do not connect to P-)
X5.2 DI 4.1 (Z)
Freely configurable digital input 4.1, 0 to 28 V, active minus or plus
X5.1 DO 4.1 (K)
Freely configurable digital output 4.1, max. 50 mA
X6.5 DO 3.2 (A)
Freely configurable digital output 3.2, max. 50 mA
X6.4 DO 3.3 (S)
Freely configurable digital output 3.3, max. 50 mA
X6.3 -
Reference potential (do not connect to P-)
X6.2 DO 4.2
Freely configurable digital output 4.2, max. 50 mA
X6.1 DO 4.3
Freely configurable digital output 4.3, max. 50 mA
No.
Name
Description (as RM/RT lines)
X1.1 DO 2.3
No function
R
T line 1
X1.2 DO 2.2
No function
X1.3 -
Reference potential (do not connect to P-)
X1.4 DO 1.3 (S)
Fault output (RT line 1), max. 50 mA
X1.5 DO 1.2 (A)
Alarm output (RT line 1), max. 50 mA
X2.1 DO 1.1 (K)
Monitoring output (RT line 1), max. 50 mA
X2.2 DI 1.1 (Z)
Reset input (RT line 1)
X2.3 -
Reference potential (do not connect to P-)
X2.4
LINIE 1 (T) RT line 1, max. 50 mA
X2.5 FE
Functional earth
X3.1
DO 2.1
No function
RM line 1
X3.2
DI 2.1
No function / Reset input fire alarm system
X3.3
-
Reference potential (do not connect to P-)
X3.4
LINIE 2 (R) RM line 1, max. 50 mA
X3.5
FE
Functional earth
X4.5
FE
Functional earth
RM line 2
X4.4
LINIE 3 (R) RM line 2, max. 50 mA
X4.3
-
Reference potential (do not connect to P-)
X4.2
DI 3.1
No function
X4.1
DO 3.1
No function
X5.5 FE
Functional earth
R
T line 2
X5.4
LINIE 4 (T) RT Line 2
X5.3 -
Reference potential (do not connect to P-)
X5.2 DI 4.1 (Z)
Reset input (RT line 2)
X5.1 DO 4.1 (K)
Monitoring output (RT line 2), max. 50 mA
X6.5 DO 3.2 (A)
Alarm output (RT line 2), max. 50 mA
X6.4 DO 3.3 (S)
Fault output (RT line 2), max. 50 mA
X6.3 -
Reference potential (do not connect to P-)
X6.2 DO 4.2
No function
X6.1 DO 4.3
No function
EM-L01
Terminal module