30/36
CPS-M1-MSE
English
99.828.70 1.2/07/22
Designation
Description
-
Reference potential / negative:
used as the reference potential for external peripherals (e.g. SHEV operation panel or
LT).
May not be connected to P-.
The reference potentials of more than one power supply module may not be connected together.
ACB.A x / ACB.B x
MOT.a x / MOT.b x
Group (ACB):
used for the connection of bus-capable drives.
ACB.A x and ACB.B x are necessary for communication with the drives.
MOT.a x and MOT.b x are necessary for supplying the connected drives.
The maximum output current of the supply is 10 A.
The supply is permanently short-circuit resistant and the fuse used is self-resetting.
ACN D+ / ACN D-
Shield
AdComNet connection:
used for interconnecting more than one CPS-M1 and for interconnecting with ACN-CM501,
ACN-IO501, ACN-BI501-USB and ACN-GW501-MRTU.
If this connection is not used, it must nevertheless be terminated with a resistor (110 Ohm).
BATT+ / BATT-
Battery connection:
may only be used for connecting the secondary power supply (battery).
COM x / NC x / NO x
(monostable, CRM
Isolated output:
used for the triggering of external systems.
The maximum contact current is 1 A.
The minimum contact current to ensure permanent safe operation is 10 mA.
The maximum contact voltage is 35 V DC.
The contact is not suitable for switching 230 V AC.
The output can be supplied with emergency power. This is to be taken into consideration in the battery capacity calcula
-
tion.
COM x / NC x / NO x
(bistable, BRM)
Isolated output:
used for the triggering of external systems.
The maximum contact current is 3 A.
The minimum contact load to ensure permanent safe operation is 5 V / 10 mA.
The maximum contact voltage is 30 V DC or 265 V AC.
DI x.x
Digital input:
used for the evaluation of switch signals.
The input voltage range is 0 V DC to 28 V DC.
The pull-up resistor for the evaluation of an active negative signal is integrated.
The pull-down resistor for the detection of an active positive signal is integrated.
The switching contact is briefly (< 100 ms) loaded with 16 mA.
The input DI 1.1 of the controller module cannot currently be used.
DO x.x
Digital output:
used for the triggering of displays or relays.
The output voltage range of an activated output is 17 V DC to 25 V DC.
The output voltage range applies for a maximum output current of 50 mA.
The connection is permanently short-circuit resistant and the fuse used is self-resetting.
If the output is deactivated, the output is open / has a high resistance.
Active negative inputs cannot be switched using the output.
The output can be supplied with emergency power. This is to be taken into consideration in the battery capacity calcula
-
tion.
FE
Functional earth:
can be used as the cable shielding connection when connecting a smoke detector line
.
May only be used as a cable shielding connection.
LINE / RT x
Line connection:
used for connecting a smoke detector line or an SHEV operation panel line. Furthermore, external
systems (e.g. fire detectors) can be connected.
LINE / RM x
A maximum of 30 smoke detectors or 10 SHEV operation panels can be connected.
The connection is permanently short-circuit resistant and the fuse used is self-resetting.
Cable monitoring is performed via the EM-L01.
MOT.A x / MOT.B x
E/HS
Group (polarity change):
used for the connection of conventional pole-changing drives.
MOT.A x and MOT.B x are necessary for the supply and for controlling the direction.
The maximum output current of the supply is 10 A.
The supply is permanently short-circuit resistant and the fuse used is self-resetting.
E/HS is used for cable monitoring and for triggering the high-speed function.
n.c.
The terminal is not connected.
N+
Operating voltage not supplied with emergency power:
used for the supply of external peripherals.
The output voltage range is 22 V DC to 24 V DC.
The maximum output current is 440 mA.
P-
Group reference potential / group negative:
used as the reference potential for external drives (e.g. spring return
actuators).
May not be connected to –.
The group reference potentials of more than one power supply module may not be connected together.
+
Operating voltage supplied with emergency power:
used for the supply of external peripherals.
The current consumption of the connected peripherals must be taken into consideration in the battery capacity calcula
-
tion.
The output voltage range is 19 V DC to 27 V DC.
The maximum output current is 440 mA.
SGI x
This function has not yet been implemented.
SNT+ / SNT-
Mains power connection:
may only be used for connecting the primary power supply (power pack).
TCSU1
Temperature sensor connection:
may only be used for connecting the TCSU1-RJ12.
The maximum cable length to ensure permanent safe operation is 2 m.
TP-C1
Touch panel connection:
may only be used for connecting the TP-C1-35-RJ12.
Description of the inputs and outputs