Intended use

-  Ventilation control for small to medium sized
  building objects
-  For triggering of 24 V DC drives
-  5 ventilation groups
-  8 A total actuating current - stabilized
-  Only for indoor mounting

Example for Application

*  optional function extension (separate components, retrofitable!)

This instruction includes descriptions and connection plans of components which are not part of 
scope of supply of control panel. You can order these parts and many more separately from your 
D+H distributor. Further connecting plans are available there as well.

WARNING

Performance features

-  Ventilation safety function (key operation
  OPEN/CLOSE), can be free encoded
-  Weather automatic for single groups,
  can be switched on and off
-  Entry for external control, e.g. timer
-  Possibility of connecting rain detector or wind/ rain
  detector without supplementary module
-  Plastic housing, surface mounted type with
  lockable steel sheet door

Delivery contents

Ventilation  control  panel  including  control  Board, 
plastic housing, replacement fuses and instructions 
for use.

groups

window drives*

vent button*

room temp. control*

Control panel (GVL 8408-M-UL)

rain sensor*

external control*

Safety notes:

-  Read all safety warnings, instructions, illustrations and specifications provided with this 

product.

-  Failure to follow all instructions listed below may result in electric shock, fire and/or serious 

injury.

-  Save all warnings and instructions for future reference.

-  When installing the Ventilation Control Panel (GVL 8304-K-UL), basic safety precautions should 

always be followed to reduce risk of fire, electric shock, and personal injury.

-  Operating voltage 115 V AC!

-  Prior to installation, maintenance and installation of additional assemblies to the control panel, 

the control panel must be separated from the supply voltage and all electrical parts nearby there 
are powered, must be covered.

-  Connection has to be carried out only by an authorized electrical specialist.

-  Mounting of the control panel should be carried out by a D+H distributor, whose qualification 

and experience is ensured by regular in-house training.

-  Only listed cable types for Class 2 circuits may be used:

a) Type CL2, CL2P, CL2R, or CL2X complying with the Standard for Power-Limited Circuit 
Cables, referenced in Annex A, Ref. No. 12, or
b) Other cable with equivalent or better electrical, mechanical, and flammability ratings; or
c) Cable that is a factory-connected integral part of a Class 2 power supply complying with the 
Standard for Class 2 Power Units, referenced in Annex A, Ref. No. 13, or a Class 2 transformer 
complying with the Standard for Low Voltage Transformers - Part 3: Class 2 and Class 3 
Transformers, referenced in Annex A, Ref. No. 11, or an LPS (Limited Power Source) supply 
complying the Standard for Information Technology Equipment - Safety - Part 1: General 
Requirements, referenced in Annex A, Ref. No. 14.

-  All wiring must be installed by a qualified electrican according to e.g. National Electrical Codes, 

NFPA 70 and local codes.

-  For continued protection against fire, replace only with the same type and rating of fuse.

-  Each control unit has provision for permanent connection to the supply source by means of 

rigid or flexible conduit or equivalent in accordance with the National Electrical Code.

-  The conduit openings shall be provided an shall be for conduit entry 22.2-mm (7/8 in.) in 

diameter or equivalent metric cable glands.

-  To create the cable entry: 

A suitable tool with depth stop must be used to create the cable entry. 
The depth stop must be set so that the central Board cannot be damaged. 

-  Duty cycle: After 2 minutes operation time, 8 minutes pause.

-  Only for indoor mounting.

-  Just use unchanged original D+H parts

For North America:

The International Building Codes have to be observed

Summary of Contents for GVL 8408-M-UL

Page 1: ...GVL 8408 M UL en Original instructions Page 2 99 828 04 1 0 06 19...

Page 2: ...al mechanical and flammability ratings or c Cable that is a factory connected integral part of a Class 2 power supply complying with the Standard for Class 2 Power Units referenced in Annex A Ref No 1...

Page 3: ...y more separately from your D H distributor Further connecting plans are available there as well Performance features Ventilation safety function key operation OPEN CLOSE can be free encoded Weather a...

Page 4: ...switch S5 group 1 5 22 12 AWG max 4 5 lb in Encoding of group DIP switches S1 S5 Following functions can be adjusted for each group separately with DIP switches S1 S5 on motherboard of control panel a...

Page 5: ...3 5 112 180 299 4 98 164 262 ft ft ft type 2x AWG 16 2x AWG 14 2x AWG 12 total current 0 5 240 400 640 1 120 200 320 1 5 80 130 213 2 60 100 160 2 5 48 80 128 3 40 65 107 3 5 34 55 91 4 30 50 80 m m...

Page 6: ...GVL 8408 M UL 99 828 04 1 0 06 19 6 12 English Connection 115 VAC supply cable tie for strain relief L N PE 115 V AC 60 Hz GVL 8408 M UL...

Page 7: ...T 84 U SD L P Mot b Mot a 24 V DC Window Drives Mot b Mot a G Az Zz External contact for central closing e g rain detector X Line lengths and cross sections see page 5 The input current of the connect...

Page 8: ...al only LT 84 U SD Vent buttons e g LT 84 U W LT 84 U SD L P Mot b Mot a 24 V DC Window Drives Mot b Mot a G Az Zz GVL 8408 M UL X Line lengths and cross sections see page 5 optional rain Wind 1 2 4 3...

Page 9: ...the system will automatically close in case of wind or rain The system will not automatically open again if wind or rain has stopped Opening of the system for ventilation via vent button The weather a...

Page 10: ...d packaging should be sorted for environmental friendly recycling Do not dispose electrical devices into household waste Disposal To avoid accidents always disconnect the ventilation control from the...

Page 11: ...yyyy BSY CDP 1500 yyyy BSY CDP TW 1600 yyyy BSY CDP TW 2000 yyyy BSY CDP TW 3000 yyyy BSY may be followed by several digits refering to optional data signals and connections configurations with yyyy t...

Page 12: ...Germany 22949Ammersbek 49 239 Tel 40 605 65 49 Fax 40 605 65 254 E Mail info dh partner com www dh partner com 2018 D H Mechatronic AG Ammersbek Technische nderungen vorbehalten Rights to technical mo...

Reviews: