GVL 8408-M
GVL 8408-M
99.824.66 1.6/03/16
99.824.66 1.6/03/16
4/8
5/8
English
English
115 V AC supply
Connection – Vent buttons and Window drives
Line lengths and
cross sections
see page 4
4
5
6
7
GVL 8408-M
–
Mot.b
Mot.a
X
OPEN
CLOSE
L
(open signal, only L
T
84-U-SD)
LT
MOT
1
2
3
Vent button
(e.g. LT 84-U-SD)
L
P
Mot.b
Mot.a
24 V DC
Window Drives
Mot.b
Mot.a
4
GVL 8408-M
+G
Az
Zz
–
X1
1
2
3
External contact
for central closing
(e.g. rain detector)
Drive group 1 ... 5
Ask your local D+H partner for further connection examples.
Wiring plan (Paragon)
115 V AC, 60 Hz
to further ones
see line lenghts and cross sections
window drive
control panel
vent button
ca. 4 ft above
upper edge
firm flooring
4x AWG 20
4x AWG 20
4x AWG 20
rain sensor
3x AWG 14
room temperature
control
Line lenghts and cross sections
total current
0.5
787
1312
2100
1
394
656
1050
1.5
262
427
699
2
197
328
525
2.5
157
262
420
3
131
213
351
3.5
112
180
299
4
98
164
262
ft
ft
ft
type
2x AWG 16
2x AWG 14
2x AWG 12
total current
0.5
240
400
640
1
120
200
320
1.5
80
130
213
2
60
100
160
2.5
48
80
128
3
40
65
107
3.5
34
55
91
4
30
50
80
m
m
m
type
2x 1,5 mm²
2x 2,5 mm²
2x 4 mm²
Encoding of group
Following functions can be adjusted for each group separately with
DIP switch S1 - S5
on motherboard
of control panel and on group plug-in unit, if available.
The delivery state of all DIP-switches is OFF.
1 = ON
Drives
CLOSE
up to final position by
single pressing
on respective vent button.
1 = OFF
Drives are closing
only so long as
the vent button is
pressed
.
2 = ON
Drives
OPEN
up to final position by
single pressing
on vent button.
2 = OFF
Drives are opening
only so long as
the vent button is
pressed
.
3 = ON
Drives are
automatically closed
by trigger of function „
Central CLOSE
",
e.g. by rain detector or room temperature control.
3 = OFF
Drives can be closed
only by pressing
the respective
vent button
.
4 = ON
Drives are
automatically opened
by trigger of function „
Central OPEN
",
e.g. by room temperature control.
4 = OFF
Drives can be opened
only by pressing
the respective
vent button
.
The input current of the
connected window drives
shall not exceed 4 Amp.
WARNING
Output voltage 24 VDC!
Do not run cables together with power lines!
In case of a cable with
ground wire
(e.g. green / yellow) this must
not be used
!
L
N
PE
115 V AC, 60 Hz
cable tie for
strain relief
external
control
2x AWG 20