background image

10/12

RZN 430x-M

Rev.:1.6

Troublesshooting

Should the smoke extraction system fail to operate satisfactorily or the green pilot light

in

the button fail to light up, check the following points.

Causes

No 230 VAC power

                  supply.

Battery faulty.

Batterie O.K.

       Fault in 

MOT

 group.

Fault in 

MOT

 group.

       Fault in 

MOT

 group.

Group O.K.

Fault in smoke-vent

button line 

RT 

or

 

in

smoke

          detector line 

RM

Line O.K.

Remedy

Call duty electrician at once to
rectify cause of power failure.

Check battery, fuse and
connections.

Check fuse, connections,
cables, terminal resistors on
drives.

Check terminal resistor or
module between terminals 

5

and 

7

.

Check terminal resistor or
module between terminals 

5

and 

6

.

Check fuse, connections,
cables, terminal resistors,
terminals, smoke-vent buttons,
smoke detectors an external
control system.

Symptoms

Power

LED

 fails to light up.

Battery

LED 

 lights up.

LED 

 fails to light up.

Group 1 or 2

LED 

 lights up.

Pilot light 

 extinguishes

during closing operation; red

LED 

 lights up; vent cannot

close.

Pilot light

extinguishes

during closing operation after

approx. 20 sec.; red LED 

lights up.

LED 

 fails to light up.

Line 1 or 2

LED 

 lights up.

LED 

 fails to light up.

Summary of Contents for RZN 4304

Page 1: ...uable property Annual function check by manufacturer or duly authorized specialist Wiring installation and functional testing only by qualified electrician The green pilot lights on the vent buttons m...

Page 2: ...2 LED DRIVES GROUP 2 fuse DIP switchblock S2 DIP switchblock S1 ALARM LINIE 2 LED FAULT LINIE 2 LED FAULT LINIE 1 LED ALARM LINIE 1 LED ALARM RESET Line ON OFF Reset detectors ALARM RESET Line ON OFF...

Page 3: ...em 400m Min clearance from walls beams etc 50cm Do not mount in airflow from ventilation systems or domelights Fire extinguishing systems must not adversely affect the detectors In case of sprinkler s...

Page 4: ...4 12 RZN 430x M Rev 1 6 Standard Connection with RT 42 11...

Page 5: ...nt button RT 42 On smoke vent buttons with a lower PCB serial no than DH4642 see rear of PCB Line connection to next smoke vent button from terminal 2 Terminal 7 is without significance Fire detectors...

Page 6: ...imate LT 43 thermal detector THE4 ye bk bk closed open signal optional open monitored Mot a Mot b L L P P bl bu br bn control alarm closed general malfunction Smoke vent button RT 43 H RT 43 N 10kW al...

Page 7: ...button each first to penultimate smoke vent button each Shunt connection by customer S general malfunction E1 Parallel Connection of Smoke Vent Buttons RT 43 H N Terminal resistors for line monitoring...

Page 8: ...ctor using the smoke heat vent button DIP switches 3 must be OFF DIP switch 4 ON The vent closes completely after the vent button has been pressed once If DIP switch 4 is OFF the vents will only close...

Page 9: ...nt button First all open the system then close it again Activate fire detectors with D H smoke detector test unit or cigarette smoke Re sponse time lag approx 20 sec The red LED must light up and the...

Page 10: ...fuse and connections Check fuse connections cables terminal resistors on drives Check terminal resistor or module between terminals 5 and 7 Check terminal resistor or module between terminals 5 and 6...

Page 11: ...which operate by thermal ascending force and by automatic fire recognition devices thermal detector smoke detector and they release either self acting or manual by smoke detectors at an early stage of...

Page 12: ...up end Example 1 1 Lane Simple wiring however unfavourable for voltage drop All drives on one line Example 2 2 lanes Control panel in the centre one side wired as branch the other one as terminal line...

Reviews: