8/12
RZN 430x-M
Rev.:1.6
DIP switch 1 from S1 and S2 ON
=
At alarm on one line the other line will be switched
on automatically, that means
all groups will open.
DIP switch 2 ON
=
In case of a line fault (e.g. break in button wiring or missing terminal
resistor), the control panel switches to alarm status, i.e. the
smoke
vent opens.
DIP switch 3 ON
=
A smoke detector alarm
cannot
be reset by pressing the button
in
the smoke/ heat vent button unit once.
If you require a remote reset facility for the smoke detector using the smoke/heat vent
button, DIP switches 3 must be OFF.
DIP switch 4 ON
=
The vent closes completely after the vent button has been pressed
once.
If DIP switch 4 is OFF, the vents will only close as long as the vent button is pressed.
After that it is no longer possible to close the vents using the smoke/ heat vent buttons
or weather control!
DIP switch 5 ON
=
The vent opens completely after the vent button has been pressed
once.
If DIP switch 5 is OFF, the vents will only open as long.
Coding line and group
The following functions can be coded on the control panel using the DIP switches on the
mainboard.
DIP switchblock
S1
codes
Line 1 and Group 1
DIP switchblock
S2
codes
Line 2 and Group 2