ON

Dip switch 1 on ON

 =

OPEN-running time limitation.

 Using a potentiometer 

sec

20

2

60

40

 , running time

in Open direction can be limited. If the vent button is actuated in Open
direction, the drive will run open as long as the running time is set.

Dip switch 2 on ON

 =

Ventilation time limitation. 

Using a potentiometer 

min

15

2

45

30

 , ventilation time

can be set. Drives will automatically close again, after the adjusted time has
expired.

Dip switch 3 on ON

 =

OPEN-retriggering. 

If Dip switch 1 is switched on ON, the OPEN-running

time limitation can be retriggered again.

Dip switch 4 on ON

 =

Power failure-CLOSED. 

If the power supply breaks down, the drive will

close. Only if Dip switch 5 = ON

Dip switch 5 on ON

 =

Ventilation flap close up to final position by single pressing on vent button.

When dip switch 5 is switched on OFF, flaps are closing only so long as the vent button
or the button 

 in the smoke vent button is pressed.

OPEN-display on vent button is no longer possible then! If Dip switch 5 is on OFF, the
function power failure-CLOSED will be ineffective (see Dip switch 4).

Dip switch 6 on ON

 =

Ventilation flap opens up to final position by single pressing on vent
button.

If Dip switch 6 is connected on OFF, the flaps will only open as long as the vent button is
pressed.

Dip switch 7 on ON

 =

The control panel will be switched on alarm, that means the 

smoke

vent opens 

at a 

line fault 

(e.g. at an interrupted detector line or short

circuit).

Dip switch 8 on ON

 =

The control panel will be switched on alarm, that means, the 

smoke vent

opens 

in case of 

group fault 

(e.g. in case of an interrupted control line).

Dip switch 8 must be on ON in conjunction with a ground in thermal maximal
detector (e.g. THE 4).

Dip switch 9 on ON 

=

Smoke detector alarm can 

not

 be reset by single pressing on button 

 in

smoke vent button.

Dip switch 9 must be switched on OFF, when remote reset is desired of smoke detectors
by the smoke vent button.

Dip switch 10 on ON 

= The smoke vent is triggered for a duration of 30 minutes in intervals of

2 minutes according to VdS 2581.

Encode of Line and Group

Following functionings can be set with Dip switch (S1) on motherboard.

Set position of
Dip-switch at delivery:

Summary of Contents for RZN 4402-K

Page 1: ...by the manufacturer Green control diodes in the buttons must constantly lighten otherwise see Informations for Starting Repair power failure at once Emergency power supply for 72 hours Approval Numbe...

Page 2: ...y the latest maintenance instructions Following tests must be carried out in the course of maintenance Outside examination inspection of system components Measuring of insulation resistances Checking...

Page 3: ...ation of German Insurer against damage of property VdS and the respective local authorities Recommended is that maintenance work should be carried out by authorized specialist companies only Only regu...

Page 4: ...nts Retrofitable System Overview Drive group signal indicating board acoustical optical alarm devices signal contact 230V 50Hz Mains supply wind rain transmitter smoke vent button min 2 piece ventilat...

Page 5: ...x 262 x 81mm Mounting of housing 1 joint rod door plaster cross for flush mounting cable cover cable bushing only surface mounting housing flush mounted wall hook optional flush mounted set UPS 44 K n...

Page 6: ...of fire walls must not be inadmissibly influenced Sound insulation is impaired by flush mounting Final mounting 3 Mount and connect central pcb 4 Screw down cable cover 5 Unhinge door of the door fra...

Page 7: ...n cover plate in control panel View motherboard RZN 4402 04 K fire recognition element thermo maximum signal fuse drive fuse external detector Dip switch mains conne ction LED failure group LED contro...

Page 8: ...in the ceiling Size kind and arrangement of the opening is of decisive significance for an optimal effect of the smoke and heat vent system The important thing here is that an escape must not be hind...

Page 9: ...H N surface 24 VDC circa 1 5m above upper edge firm flooring by customer 55mm flush socket Vent button 24 VDC e g LT 43 circa 1 2 above upper edge firm flooring at flush type by others 55mm flush sock...

Page 10: ...e by thermal ascending force and by automatic fire recognition devices thermal detector smoke detector and they release either self acting or manual by smoke detectors at an early stage of a fire and...

Page 11: ...pinched in control panel for transport Take it off there and connect according to plan Terminal resistors must remain at binder RM 1 2 when no fire detector or external control exists Fire detectors...

Page 12: ...12 20 RZN 4402 04 K Rev 3 8 Parallel Connection of Smoke Vent Buttons RT 42...

Page 13: ...re pinched in control panel for transport Take it off there and connect according to plan Terminal resistors must remain at binder RM 1 2 when no fire detector or external control exists Fire detector...

Page 14: ...02 04 K line line control alarm close RM RT smoke vent button RT 43 H smoke vent button RT 43 N 10kW 10kW alarm alarm control control line line line line malfunction close close 2 2 7 8 7 3 3 1 1 6 6...

Page 15: ...15 20 RZN 4402 04 K Rev 3 8 Parallel Connection of 2 x 2 Smoke Vent Buttons RT43 H N...

Page 16: ...Magnetic clamp The resistor must not be used when line connections with 2 detector dependency are employed Connection of several fire detectors Connection of one fire detector terminal resistor line 1...

Page 17: ...wires Mot a Mot b derive off in par allel monitoring will be looped through all cables up to group end Example 1 1 line Simple installation but unfavourable for voltage drop All drives on one line Exa...

Page 18: ...be reset under special conditions only Performance check alarm reset and ventilation 10k resistance in smoke vent button 10k resistance in fire detector Stop module 2x47k in conduit box Connect mains...

Page 19: ...ossible then If Dip switch 5 is on OFF the function power failure CLOSED will be ineffective see Dip switch 4 Dip switch 6 on ON Ventilation flap opens up to final position by single pressing on vent...

Page 20: ...red display diode extinguishes in button and control panel Smoke vent must close Automatic fire detectors Release smoke detector individual by D H smoke detector tester as an alternative by cigarette...

Reviews: