9/20
RZN 4402/04-K
Rev.:3.8
M
230VAC
24VDC
Brandmelder
Zentrale
Antrieb
230V 50Hz
nicht abschaltbar
Kontakt
Fremdansteuerung
Rauchabzugstaster
Rauchabzugstaster
zu weiteren
zu weiteren
M
IY (St) Y
2x2x0,6
IY (St) Y
2x2x0,6
IY (St) Y
2x2x0,6
IY (St) Y
4x2x0,6
IY (St) Y
4x2x0,6
230VAC
24VDC
siehe Kabelverlegetabelle
im obersten bewohnten Geschoss
im EG
Lüftungstaster
Legend
Drive 24 VDC at smoke vent flap
(lines must end in flush
mounted distribution box, see
symbols above).
RZN surface or flush type
(230 VAC / 24 VDC)
in proximity of smoke vent flap.
Smoke vent button
(e.g. RT 43-H/N) surface 24 VDC
circa 1,5m above upper edge
firm flooring (by customer 55mm
flush socket)
Vent button 24 VDC (e.g. LT 43)
circa 1,2 above upper edge firm
flooring (at flush type by others
55mm flush socket)
Fire detector 24 VDC
(e.g. FO 1362 or FT 1262)
Wiring Plan (Paragon)
Drive
see cable wiring table
to further ones
to further ones
Control
panel
not possible to switch off
Fire detector
Ventilation
button
Contact external control
230 V Supply
Provide for separate electric circuit.
Mark fuses.
Plug covering cap over mains binder on
motherboard of control panel.
Connecting cable:
NYM-I 3x1.5
Connecting load:
RZN 4402-K = 60 VA
RZN 4404-K = 120 VA
Weak Current Lines
Install and feed separately from supply
mains.
Mark cable and terminal box red.
Secondary control
Main control