background image

9/20

RZN 4402/04-K

Rev.:3.8

M

230VAC

24VDC

Brandmelder

Zentrale

Antrieb

230V 50Hz

nicht abschaltbar

Kontakt
Fremdansteuerung

Rauchabzugstaster

Rauchabzugstaster

zu weiteren

zu weiteren

M

IY (St) Y
2x2x0,6

IY (St) Y
2x2x0,6

IY (St) Y
2x2x0,6

IY (St) Y
4x2x0,6

IY (St) Y
4x2x0,6

230VAC

24VDC

siehe Kabelverlegetabelle

im obersten bewohnten Geschoss

im EG

Lüftungstaster

Legend

Drive 24 VDC at smoke vent flap
(lines must end in flush
mounted distribution box, see
symbols above).

RZN surface or flush type
(230 VAC / 24 VDC)
in proximity of smoke vent flap.

Smoke vent button
(e.g. RT 43-H/N) surface 24 VDC
circa 1,5m above upper edge
firm flooring (by customer 55mm
flush socket)

Vent button 24 VDC (e.g. LT 43)
circa 1,2 above upper edge firm
flooring (at flush type by others
55mm flush socket)

Fire detector 24 VDC
(e.g. FO 1362 or FT 1262)

Wiring Plan (Paragon)

Drive

see cable wiring table

to further ones

to further ones

Control

panel

not possible to switch off

Fire detector

Ventilation

button

Contact external control

230 V  Supply

Provide for separate electric circuit.
Mark fuses.
Plug covering cap over mains binder on
motherboard of control panel.
Connecting cable:

NYM-I 3x1.5

Connecting load:

RZN 4402-K = 60 VA
RZN 4404-K = 120 VA

Weak Current Lines

Install and feed separately from supply
mains.
Mark  cable and terminal box red.

Secondary control

Main control

Summary of Contents for RZN 4402-K

Page 1: ...by the manufacturer Green control diodes in the buttons must constantly lighten otherwise see Informations for Starting Repair power failure at once Emergency power supply for 72 hours Approval Numbe...

Page 2: ...y the latest maintenance instructions Following tests must be carried out in the course of maintenance Outside examination inspection of system components Measuring of insulation resistances Checking...

Page 3: ...ation of German Insurer against damage of property VdS and the respective local authorities Recommended is that maintenance work should be carried out by authorized specialist companies only Only regu...

Page 4: ...nts Retrofitable System Overview Drive group signal indicating board acoustical optical alarm devices signal contact 230V 50Hz Mains supply wind rain transmitter smoke vent button min 2 piece ventilat...

Page 5: ...x 262 x 81mm Mounting of housing 1 joint rod door plaster cross for flush mounting cable cover cable bushing only surface mounting housing flush mounted wall hook optional flush mounted set UPS 44 K n...

Page 6: ...of fire walls must not be inadmissibly influenced Sound insulation is impaired by flush mounting Final mounting 3 Mount and connect central pcb 4 Screw down cable cover 5 Unhinge door of the door fra...

Page 7: ...n cover plate in control panel View motherboard RZN 4402 04 K fire recognition element thermo maximum signal fuse drive fuse external detector Dip switch mains conne ction LED failure group LED contro...

Page 8: ...in the ceiling Size kind and arrangement of the opening is of decisive significance for an optimal effect of the smoke and heat vent system The important thing here is that an escape must not be hind...

Page 9: ...H N surface 24 VDC circa 1 5m above upper edge firm flooring by customer 55mm flush socket Vent button 24 VDC e g LT 43 circa 1 2 above upper edge firm flooring at flush type by others 55mm flush sock...

Page 10: ...e by thermal ascending force and by automatic fire recognition devices thermal detector smoke detector and they release either self acting or manual by smoke detectors at an early stage of a fire and...

Page 11: ...pinched in control panel for transport Take it off there and connect according to plan Terminal resistors must remain at binder RM 1 2 when no fire detector or external control exists Fire detectors...

Page 12: ...12 20 RZN 4402 04 K Rev 3 8 Parallel Connection of Smoke Vent Buttons RT 42...

Page 13: ...re pinched in control panel for transport Take it off there and connect according to plan Terminal resistors must remain at binder RM 1 2 when no fire detector or external control exists Fire detector...

Page 14: ...02 04 K line line control alarm close RM RT smoke vent button RT 43 H smoke vent button RT 43 N 10kW 10kW alarm alarm control control line line line line malfunction close close 2 2 7 8 7 3 3 1 1 6 6...

Page 15: ...15 20 RZN 4402 04 K Rev 3 8 Parallel Connection of 2 x 2 Smoke Vent Buttons RT43 H N...

Page 16: ...Magnetic clamp The resistor must not be used when line connections with 2 detector dependency are employed Connection of several fire detectors Connection of one fire detector terminal resistor line 1...

Page 17: ...wires Mot a Mot b derive off in par allel monitoring will be looped through all cables up to group end Example 1 1 line Simple installation but unfavourable for voltage drop All drives on one line Exa...

Page 18: ...be reset under special conditions only Performance check alarm reset and ventilation 10k resistance in smoke vent button 10k resistance in fire detector Stop module 2x47k in conduit box Connect mains...

Page 19: ...ossible then If Dip switch 5 is on OFF the function power failure CLOSED will be ineffective see Dip switch 4 Dip switch 6 on ON Ventilation flap opens up to final position by single pressing on vent...

Page 20: ...red display diode extinguishes in button and control panel Smoke vent must close Automatic fire detectors Release smoke detector individual by D H smoke detector tester as an alternative by cigarette...

Reviews: