RZN 4404-K

25

/

36

DIP switch settings 

Delivery condition S1

1

2

3

4

5

6

7

8

9

10

ON

1 = ON 

OPEN-running time limitation in ventilation operation (Only if DIP switch 6 = ON).

Using a potentiometer, running time in OPEN direction can be limited.  
If the vent button is  actuated in OPEN direction, the drive will run open as long as 
the running time is set.

2 = ON 

Ventilation time limitation (Only if DIP switch 5 = ON).

Using a potentiometer, ventilation tim can be set.
Drives will automatically  close again, after the adjusted time has expired.

3 = ON 

OPEN-retriggering (Only if DIP switch 1 = ON)

The OPEN-running time limitation can be retriggered again.

4 = ON 

Power failure "CLOSE" (Only if DIP switch 5 = ON).

In case of power failure the drives will close.

5 = ON 

Drives 

CLOSE 

up to final position 

by single pressing

 on vent button

5 = OFF 

Drives are 

closing only so long as

 the vent button or the button "close SHEV" in the

smoke vent button 

is pressed

. OPEN-display on vent button is no longer possible then!

The function power failure-CLOSE will be ineffective (see DIP switch 4).

6 = ON 

Drives 

OPEN

 up to final position 

by single pressing

 on vent button.

6 = OFF 

Drives are 

opening only so long

 

as

 the vent button 

is pressed

.

7 = ON 

In case of a 

line fault

 (e.g. at an interrupted detector line or short circuit) the control panel 

will be switched on alarm, that means 

the smoke vent opens

.

8 = ON 

In case of a 

group fault

 (e.g. in case of an interrupted monitoring line) the control panel will

   be switched on alarm, that means 

the smoke vent opens

.

 DIP switch must be on ON in conjunction with a ground in thermal maximal detector (e.g.
THE4).

9 = ON 

Smoke detector alarm 

can not

 be reset by single pressing on the button "close SHEV" in 

the smoke vent button.

9 = OFF 

Smoke detector alarm 

will be

 reset by pressing on the button "close SHEV" in the smoke

vent button.

10 = ON 

SHEV retriggering on.

 The smoke vent is triggered for a duration of 30 minutes in intervals

of 2 minutes according to VdS 2581.

min

15

2

45

30

sec

20

2

60

40

Cables for D+H smoke an heat vent systems

When selecting and installing the cables, the 
regional electrical installation regulations 
concerning wiring systems and the necessary 
safety equipment, or guidelines on integrity 
maintenance of electric lines are observed (e.g. 
MLAR).

Notice:

No type designation is given  for these cables, 
because of a large variety on the market.
Please consult your D+H partner.

Wiring plan (Paragon)

Line lenghts and cross sections

Cross section  (mm²) =

Cable lenght (m) x Total current 

80

RZN 4404 - K

0,5

240
400

1

120
200

1,5

80

130

2

60

100

2,5

48
80

3

40
65

3,5

34
55

4

30
50

m
m

Type 

Total current

 3 x 1,5 mm²
 3 x 2,5 mm²

Group cable (control panel - drive)

At least three wire design:
- 2 wires for the supply of the drive
- 1 wire for line monitoring, on which also the 
SHEV high speed (HS) signal is transmitted to the 
drive. If group DIP switch 8 is ON, the group will in 
case of a fault automatically triggered and opens.

Line cable (control panel - detector)

The cables are monitored for short circuit and for 
interruption. If line DIP switch 7 is ON, the group 
will in case of a fault automatically triggered and 
opens.

230 V, 50 Hz

Seperate electric circuit.
Mark fuse.

to further ones

see line lenghts and cross sections

Drive at smoke 
vent opening

SHEV control panel

Vent button 

approx. 1,2 m 
above upper edge 
firm flooring

Smoke vent button

approx. 1,5 m above 
upper edge firm flooring

External control

4x 0,8 Ø

6x 0,8 Ø (RT 45)
10x 0,8 Ø (RT 45-LT)

6x 0,8 Ø (RT 45)
10x 0,8 Ø (RT 45-LT)

2x 0,8 Ø

2x 0,8 Ø

OK

OK

Rain detector

3x 0,8 Ø

System voltage 24 V!
Do not run cables with together power lines!
In case of a cable with ground wire (green / 
yellow) this must not be used!
Cable and terminal boxes have to be labeled.

English

Fire detector

SD-O 371 or FD-T 271

Summary of Contents for RZN 4404-K V2

Page 1: ...RZN 4404 K V2 RZN 4404 K V2 ZP RZN 4404 K V2 GEH KST 0786 CPD 50383 EN 12101 10 2005 AC 2007 conform RZN 4404 KS V2 ZP RZN 4404 K V2 GEH S RWA Original instructions...

Page 2: ...Mounting of SHEV control panel with housing GEH KST 6 View motherboard 7 DIP switch settings 8 Cables for D H smoke an heat vent systems Wiring plan Paragon 9 230 V supply 10 Connection overview 10 C...

Page 3: ...disposal to professionally install your system and commission it Our partner system guarantees that D H products are installed exclusively by trained and experienced fitters in compliance with the te...

Page 4: ...been authorized by the appliance manufacturer Servicetimer Inspection and maintenance has to be carried out according to D H maintenance notes Only original D H spare parts may be used Repair is to be...

Page 5: ...s protection IP30 IP54 Protection class II with fuctional ground I Dimensions WxHxD 310 x 310 x 100 mm 400 x 300 x 120 mm Technical data SHEV alarm Malfunction Mains existing Vent button function OPEN...

Page 6: ...RE FUM ROOKAFVOER R G L E M ODDYMIANIE EVACUACI N DE HUMOS DESENFUMAGE ODVOD KOU E ODVOD DYMU BRANDVENTILATION 2 x 1 2 A h 2 x 3 4 A h max 5 mm not included 4x Install batteries Position of the centra...

Page 7: ...gnal DIP switch S1 Fuse mains Battery charging voltage regulator Battery connection LED battery fault Fuse battery OPEN running time limitation Ventilation time limitation Line ON OFF RESET D1 D47 D42...

Page 8: ...ose SHEV in the smoke vent button is pressed OPEN display on vent button is no longer possible then The function power failure CLOSE will be ineffective see DIP switch 4 6 ON Drives OPEN up to final p...

Page 9: ...ne monitoring on which also the SHEV high speed HS signal is transmitted to the drive If group DIP switch 8 is ON the group will in case of a fault automatically triggered and opens Line cable control...

Page 10: ...l after mains cable has been connected L N PE 2 8 3 1 6 4 7 5 RT 45 2 8 3 1 6 4 7 5 RT 45 2 8 3 1 6 4 7 5 OK Line T R A K E A a Z b S RZN 4404 K V2 Line N Control Alarm CLOSE Mot b Mot a Monitoring OP...

Page 11: ...re 3 4 5 6 7 8 RZN 4404 K V2 Line Control Alarm CLOSE RM 10kW Alarm Control Line Line CLOSE Failure Shunt connection by customer Alarm Control Line CLOSE Failure n c RT 2 8 3 1 6 4 7 5 RT 45 2 8 3 1 6...

Page 12: ...minutes according to VdS 2581 For this the drives must be blockage safe All D H drives meet this precondition Otherwise the DIP switches has to be switched on OFF Mounting of the drives Please take m...

Page 13: ...lete connection of components can cause malfunction Check following connections mains 230 V drives smoke vent buttons when necessary fire detectors and vent buttons See wiring an connection plans page...

Page 14: ...ol Manual opening by smoke vent button Automatic opening by fire detector Automatic opening by external control e g fire alarm system OK SMOKE VENT OK Reset 0 I System Line D47 D42 D20 OK OK RT RZN Re...

Page 15: ...f non resettable alarm Reset OFF ON Reset 0 I System Line OK click OFF Reset 0 I System Line OK With manual release In case of automatic release by fire detector or external control External control o...

Page 16: ...n Do not ventilate via smoke vent button because otherwise there would be a danger of damage by wind or water The weather automatic can be switched off via an optional automatic switch if gap ventilat...

Page 17: ...units Functional testing of connected system components Record of competent carrying out of maintenance and designation according to directions Inspection Regular visual inspection between maintenance...

Reviews: