RZN 4503-T
RZN 4503-T
99.825.18 2.1/10/13
99.825.18 2.1/10/13
24
/
36
25
/
36
View motherboard
Signalling relais
max. 60 V / 1 A
1
Signalling relais 2
max. 60 V / 1 A
Fuse
DRIVES F 2.5 A
Mains supply
Terminal assignment
see right
OK
Signalling relais
Factory-settings
Overview control elements
r
e
w
o
P
C
A
V
0
3
2
ry
te
at
B
Detector Line
Drive
Group
Module
Connector
X2
OFF
Service
X1
0
Reset
/
I
S1
8
1
ON
Display "system OK"
DIP switch
(see page 25)
Display "mains"
Display "alarm"
Display "group fault"
Display "battery fault"
Display
"earth fault"
Display
"line fault"
Display "general fault"
Display
"not closed"
Vent button
"CLOSE"
Button "Open SHEV / Alarm"
Button "Close SHEV / Reset"
Vent button
"OPEN"
Button "Line ON / OFF"
–
: Not emergency-supplied
potential -
+
: Emergency-supplied
pot
N–
: Not emergency-supplied
potential -
N+
: Not emergency-supplied
pot
A
: General alarm
K
: Control
S
: General fault
M
: Magnetic clamp control
Z
: Input, central function,
closing of group
B
: FAS input
1 = ON
Drives
CLOSE
up to final position
by single pressing
on vent button.
1 = OFF
Drives are
closing only so long
as the vent button or the button "close SHEV" in the smoke
vent button
is pressed
.
2 = ON
Drives
OPEN
up to final position
by single pressing
on vent button.
2 = OFF
Drives are
opening only so long
as the vent button
is pressed
.
3 = ON
In case of a
line fault
(e.g. at an interrupted detector line or short circuit) the control panel
will be switched on alarm, that means
the smoke vent opens
.
4 = ON
In case of a
group fault
(e.g. in case of an interrupted monitoring line) the control panel will
be switched on alarm, that means
the smoke vent opens
.
DIP switch must be on ON in conjunction with a ground in thermal maximal detector (e.g.
THE4).
5 = ON
OPEN-running time limitation in ventilation operation (Only if DIP switch 2 = ON)
If the vent button is actuated in direction OPEN, the drives open for 30 s (factory-set).
This running time can be edited by PDA servicetool.
6 = ON
Ventilation time limitation (Only if DIP switch 1 = ON)
The drives will automatically close again after the time set (factory-set 10 min).
This time can be edited by the PDA servicetool.
7 = ON
Power failure "CLOSE" (Only if DIP switch 1 = ON)
In case of power failure the drives will close.
8 = ON
Integrated
ventilation buttons
are
activitated
.
8 = OFF
Integrated
ventilation buttons
are
deactivitated
.
The following functions are (de-) activatable with the PDA-Service Tool:
-
OPEN running time retriggering (factory-set: deactivated)
-
Group CLOSE in case of alarm (factory-set: deactivated)
-
Two smoke detectors dependency (factory-set: deactivated)
-
Smoke detector alarm remote reset (factory-set: activated)
-
Lamp test
-
Alarm re-clocking (factory-set: activated)
Hint: In case of alarm the smoke vent is triggered with an OPEN pulse every 2 minutes for a
duration of 30 minutes according to VdS 2581. For this, the drive must be protected against
blockage according to VdS 2580 par. 4.7. . All D+H drives meet this precondition.
-
The signalling relay features the following signals:
pre-alarm, terminated alarm, delayed alarm, general fault, battery fault, line fault,
group fault, power failure, earth fault, passing on of "central CLOSE", "Reset Alarm" as
pulse, group closed longer = x sec. (factory-settings: signalling relais 1="alarm"
signalling relais 2 = "general fault")
1
2
3
4
5
6
7
8
ON
Delivery state
DIP switch settings
English
English