background image

99.824.43 1.4/04/16

5/16

English

 

SHD 54/450-V /-BSY+

SHD 54/450-V /-BSY+

SHD 54/450-V

for sash dimension up to (WxH): 1,2 x 1 m

SHD 54/450-BSY+

for sash dimension up to (WxH): 1,2 x 2 m

The example is just a recommendation

Mounting informations

Intended use

- Chain drive for electric opening and closing of

side hung sashes up to 65°

- Operating voltage 24 V DC
- Useable for smoke ventilation, D+H Euro-SHEV

according to DIN EN 12101-2 as well as daily
natural ventilation

Drive unit with 2,5 m silicon-cable, 
mounting template and bracket set.

Extent of supply

Safety extra low voltage 24 V DC!

Do not connect directly to the mains supply!
- Connection has to be carried out only by an

authorized electrical specialist

- Danger of violent pressure in handaccessible area
- Keep away people from the operating area of

the drive

- Keep away children from the control
- Use only in dry rooms
- Only for inside mounting

Use rain detector with danger of rain

- Just use unchanged original D+H parts

Observe enclosed red safety slip!

Safety notes

Performance features

- Microprocessor controlled synchro electronics

BSY+ for a precise synchronous run

- Individually programmable via software SCS
- Electronic limit stop and overload cutoff
- Power supply possible from left or right
- Locking relief after closing

Example for application

2 x SHD 54/450-BSY+ and  FRA 11-BSY+ 
(loking bar drive optional)

86,5

60

100

102

Space required

 Technical data

Type 

SHD 54/450-V /-BSY+

Observe double current consumption for the „-BSY+ Set“ version!

Rated voltage 

24 VDC, ± 15%; 1A 

Performance 

24 VA

Push/ pull force 

500 N + ca. 20 % switch-off reserve (temporary)

Clamping force 

ca. 250 N  

Runtime-OPEN 

ca. 12 mm/s

Runtime-CLOSED 

ca. 12mm/s

Lifetime 

>20 000 double strokes

Duty cycle 

30 % (With cycle time 10 min.)

Fire stability 

30 min. / 300°C

Housing 

Aluminium powder-coated (~RAL 9006)

Ingress protection 

IP 50

Temp. range 

-5 ... +75°C

Emission sound pressure level 

LpA ≤ 70 dB(A)

Electrical devices, accessories, batteries and packa-
ging  should  be  sorted  for  environmental-friendly 
recycling.  Do  not  dispose  electrical  devices  and 
batteries into household waste!
Only for EC countries:
According the European Guideline 2012/19/EU for 
waste  electrical  and  electronic  equipment  and  its 
implementation into national right, electrcal devices 
that are no longer usable must be collected separa-
tely  and  disposed  of  in  an  environmentally  correct 
manner.

Disposal

Declaration of Conformity

We  declare  under  our  sole  responsibility  that  the 
product  described  under  “Technical  Data”  is  in 
conformity with the following directives:

2014/30/EU, 2014/35/EU

Technical file at:
D+H Mechatronic AG, D-22949 Ammersbek

Dirk Dingfelder

Maik Schmees

Member of the Board 

Authorized signatory, Technical Director

31.03.2016

Maintenance and cleaning

Maintenance work is only allowed when the device is in
a de-energized condition! Inspection and maintenance 
has to be carried out according to D+H maintenance 
notes.  Only original  D+H  spare  parts  may  be used. 
Repair is to be carried out exclusively by D+H.
Wipe away debris or contamination  with a  dry,  soft 
cloth.
Do not use cleaning agents or solvents.

Guarantee

You will get 2 years guarantee for all D+H products 
from date of verified handing over of the system up to 
maximal  3  years  after  date  of  delivery, when 
mounting  and  starting  has  been  carried  out  by  an 
authorized D+H-distributor.
D+H guarantee is expired, with connection of D+H 
components with external systems or with mixing of 
D+H products with parts of other manufacturers.

WARNING

Read all safety warnings, instructions, illustrations 
and specifications provided with this product.
Failure to follow all instructions listed below may 
result in electric shock, fire and/or serious injury.
Save all warnings and instructions for future 
reference.

Summary of Contents for SHD 54/450-V

Page 1: ...SHD 54 450 V BSY instructions...

Page 2: ...features Microprocessor controlled synchro electronics BSY for a precise synchronous run Individually programmable via software SCS Electronic limit stop and overload cutoff Power supply possible from...

Page 3: ...nsibility that the product described under Technical Data is in conformity with the following directives 2014 30 EU 2014 35 EU Technical file at D H MechatronicAG D 22949Ammersbek Dirk Dingfelder Maik...

Page 4: ...YE YE BN WH SHD 54 450V Mot b Mot a BRV Mot b out Mot a out Signal Mot b in Mot a in BK BK OG EM 47 K SHD 54 450 V FRA 11 BSY SHD 54 450 V BSY Standard WH Mot a BN Mot b YE BRV 2x47kW Junction box En...

Page 5: ...own BK black OG orange YE yellow GN green PK pink VT violet GY grey Not in case of GVL E K M Cable according to D H table for layout of cables see instructions for use control panel SHD 54 450 V FRA 1...

Page 6: ...YE GN WT BN YE GN Data b Data a Mot b in Mot a in Mot b Mot a Data b Data a WT BN YE GN Mot b Mot a Data b Data a BK BK OG EM 47 K Option BRV WH Mot a BN Mot b n c YE Data A GN Data B GY BRV Standard...

Page 7: ...A 11 BSY Not in case of GVL E K M Cable according to D H table for layout of cables see instructions for use control panel If necessary VP signal must be activated via SCS SHD 54 450 BSY FRA 11 BSY WH...

Page 8: ...d be fore drive op eration pu ll ou t the pin an d remov e this lab el Na ch Mon tage un d vo r Inbe trieb na hm e de s An trieb es de n Bo lzen zieh en un d die se s Etike tt en tfe rnen 5 0 0 m m 5...

Page 9: ...installatio n an d be fore drive op eration pu ll ou t the pin an d remov e this labe l Nac h Mon tage un d vo r Inbe trieb na hm e de s Antrie be s de n Bolze n zieh en un d dies es Etik ett en tfe r...

Page 10: ...Dyer Environmental Controls Ltd Unit 10 Lawnhurst Trading Estate Cheadle Heath Stockport SK3 0SD Tel 44 0 161 491 4840 E Mail enquiry dyerenvironmental co uk www dyerenvironmental co uk...

Reviews: