ZA-K-BSY+

99.823.99 1.7/02/16

6/20

ZA-K-BSY+

 

Drive unit with 2.5 m silicone cable. Depending on 
the  type  of  window, different  bracket  sets  are 
available separately.

Scope of supply

Type 

ZA 35-K-BSY+(-HS) 

ZA 85-K-BSY+(-HS) 

ZA 105-K-BSY+(-HS)  ZA 155-K-BSY+(-HS)

Supply 

230 V AC, +10 % / -15 %, 50 Hz

Active power 

20 W (35 W)  

30W (50 W) 

35 W (60 W)  

45 W (75 W)

Apparent output 

30 VA (45 VA) 

45 VA (75 VA) 

55 VA (85 VA) 

70 VA (105 VA)

Nominal force 

300 N  

800 N  

1000 N 

1500 N

Nominal locking force 

1100 N

Service life 

>20 000 double strokes

Duty cycle 

30 % S2 (EN 60034-1), no continuous voltage

Housing  

aluminium / polycarbonate

Ingress protection 

IP 65 (“-W“ = IP 54)

Temperature range 

-5 ... +75°C

Fire stability 

30 min / 300°C

Emission sound pressure  LpA ≤ 70 dB(A)
level
Nominal stroke length * 

see type plate

Additional functions * 

Closing edge protection activated (3 stroke repeatings)

* programmable with software SCS and BI-BT2 via Bluetooth

All approx.
20% cut-off reserve
(temporary)

OPEN

Forces

CR 

III

CR 

II

CR 

I

300 N
300 N
300 N
300 N

800 N
800 N
800 N
800 N

1000 N
1000 N
1000 N

800 N

1500 N
1000 N
1000 N

800 N

ZA 35

ZA 85

ZA 105 ZA 155

I

III

77mm

23mm

7,1 mm/s

5 mm/s

5 mm/s

II

Closing ranges

Technical data

C

LO

S

E

Safety notes

Operating voltage 230 V AC!
Risk of injury from electric shock!
Do not reverse L+N! Connect PE!
The BSY+ bus also operates with 230 V!

-   Connection must be carried out by a certified 

electrical technician

-   Danger of crushing hands and fingers!
-   Keep people away from the operating area of

   the drive

-   Keep children away from the control
-   Observe pressure load diagram of the gear  rack!
-   Use only in dry rooms
-   Suitable for indoor mounting only. Use rain

   detector in the event that there is a risk of rain

-   Use option "-W" if mounted outdoors!
-   Use unmodified original D+H parts only
-   Observe the bracket-set mounting instructions

Observe enclosed red safety note!

* only with BI-BT2 (electronically isolated due  to Bluetooth)

-   Rack  and  pinion  drive  for  electric  opening  and 

closing  of  windows  and  flaps  in  the  facade  and 
roof area

-   Operating voltage 230 V AC
-   Up to 4 drives possible
-   Useable for smoke extraction, D+H Euro-SHEV in 

accordance with DIN EN 12101-2 as well as daily 
ventilation

-   Suitable for indoor mounting only

Intended use

-   Microprocessor-controlled synchronous

   electronics BSY+ for safe and precise
   synchronous running of up to 4 drives

-   Individually programmable via software SCS*
-   SHEV-high speed function (fast-running feature in

   OPEN-direction) 

-   Closing edge protection for the main  closing edge
-   Especially quiet motor running in ventilation mode
-   Optinal with "-AS2" = protection class 2 and 

   "-AS3" as well as "-LS" = protection class 3

Features

Closing edge protection

In  the  "CLOSE"  direction  the  drive  has  an  active 
protection for the main closing edge. If there is an 
overload in the closing range 3 and 2, the drive runs 
"OPEN" for 10 seconds, then "CLOSE" again. If after 
three  attempts  closing  is  not  possible,  the  drive 
remains in this position.
In addition, the drive is equipped with passive pinch 
protection. The closing speed in closing range 2 and 
1 is reduced to 5 mm/s.

Significantly greater forces can be
exerted at the secondary closing
edges. Danger of crushing hands and
fingers!

main closing edge

beside closing edge

beside closing edge

Mounting information

-   Swivel radius of the drive must go free over entire

   range of stroke.  Otherwise, the toothed rack and
   the suspension can be damaged.

-   Drives with a stroke of ≥800 mm must not be moun-

   ted „hung up  at the bottom“ (e.g. bracket UK).

-   The drive set will be full configured by factory.

   The drives must be reconfigured in case of
   alterations (e.g. removing of drives from existing
   set or integrating a new drive) with SCS*.

-   Use only drives with the same force. 
-   Ensure evenly load distribution on all the drives.
-   Eyebolt has to be adjusted so, that the drive is

   disconnected with  closed flap through it’s inside
   stop position damping.    Brackets can be damaged
   by to rigid adjustment!

500

600

800

1000

1

100

1200

1300

1400

1500

1600

0

200

400

600

800

1000

1200

1400

max. Load (N)

Stroke (mm)

durable

temporary

Pressure load diagram

Maximum  pressure  load  of  the  toothed  rack  is  not 
automatically identical with maximum pressure force 
of the drive!
Loads from over 1000 N to 1500 N are only briefly 
permissible (e.g. to throwing off snow or with wind 
loads). These may arise up to a stroke of 800 mm.

Normal operation =

fast-mode SHEV  =

Running speeds and forces 

~7,1 mm/s /   

   ~9 mm/s (-HS: ~17 mm/s)

WARNING

Read all safety warnings, instructions, illustrations 
and specifications provided with this product.
Failure to follow all instructions listed below may 
result in electric shock, fire and/or serious injury.
Save all warnings and instructions for future 
reference.

Summary of Contents for ZA 35-K-BSY+

Page 1: ...Standard version Version without tube option OT Please order bracket sets separately ZA 35 85 105 155 K BSY HS instructions...

Page 2: ...eature in OPEN direction Closing edge protection for the main closing edge Especially quiet motor running in ventilation mode Optinal with AS2 protection class 2 and AS3 as well as LS protection class...

Page 3: ...ary OPEN Forces CR III CR II CR I 300 N 300 N 300 N 300 N 800 N 800 N 800 N 800 N 1000 N 1000 N 1000 N 800 N 1500 N 1000 N 1000 N 800 N ZA 35 ZA 85 ZA 105 ZA 155 I I I I 7 7 m m 2 3 m m 7 1 m m s 5 m...

Page 4: ...YE Data A BN L CLOSE BK L OPEN BU N 230 V AC Option SGI GN Data B YE Data A BN L CLOSE BK L OPEN BU N 230 V AC 230 V AC Standard GN Data B YE Data A BN L CLOSE BK L OPEN BU N Mounting examples triangu...

Page 5: ...s and packa ging should be sorted for environmental friendly recycling Do not dispose electrical devices and batteriesinto householdwaste Only for EC countries According the European Guideline 2012 19...

Page 6: ...circuit Programmable via SCS software and BI BT 2 Plug in the BI BT 2 only under tempered conditions RISK OF ELECTRIC SHOCK MOTOR Data a Data b SCS 30 006 23 BI BT 2 2x Size AA LR6 1 5V Co nn ect ed...

Page 7: ...on box L N PE 230 V AC 50 Hz 1 2 BU YE GN BN YE GN N PE Data a Data b ZA K BSY Slave 1 BK BU YE GN BN YE GN N PE Data a Data b ZA K BSY Master 2 BK L L L L GN green YE yellow BU blue BN brown BK black...

Page 8: ...6 0 46 104 9 13 6 30 30 9 7 Version without tube option OT 216 9 13 30 55 Nominal stroke 223 Dyer Environmental Controls Ltd Unit 10 Lawnhurst Trading Estate Cheadle Heath Stockport SK3 0SD Tel 44 0 1...

Reviews: