CDN36X User Manual
revision 1.30
Power Up Gateway
Connect the gateway to a DeviceNet network to power up the gateway.
DeviceNet Status LEDs
The CDN36X gateway has two bi-color status LEDs (
NET
and
MOD
) that indicate operational
status. During power-up, the LEDs cycle through a sequence of alternating red and green. After
power-up, the
NET
LED should be flashing green (or solid green if allocated to a DeviceNet
master) and the
MOD
LED should be solid green. If this does not occur, disconnect from
DeviceNet and verify all the switch settings. See Chapter 8 for additional troubleshooting topics.
State
DeviceNet Status LED (NET)
Off
No
power.
Flashing Red
Configuration error. Check DeviceNet switch settings.
Solid Red
Unrecoverable error.
Flashing Green
Device not allocated to a DeviceNet master.
Solid Green
Normal runtime, device allocated as a slave.
State
Module
Status
LED
(MOD)
Off
No
power.
Flashing Red
Configuration error. Check object attribute settings.
Solid Red
Unrecoverable error.
Flashing Green
Not defined.
Solid Green
Normal Operation.
Serial Channel Status LEDs
The gateway has two bi-color LEDs to indicate serial channel activity. The
TX
LED flashes
green when a packet is being transmitted. The
RX
LED flashes green when a packet is being
received. A fault is indicated by solid red. After power-up, both LEDs should be off.
State
Transmit
Status
LED
(TX)
Off
No
data
being
transmitted
Flashing Red
Not defined
Solid Red
Transmit error (parity or overrun error)
Flashing Green
Data being transmitted
Solid Green
Not defined
State
Receive
Status
LED
(RX)
Off
No
data
being
received
Flashing Red
Not defined
Solid Red
Receive error (parity or overrun error)
Flashing Green
Data being received
Solid Green
Not defined