Table 13-2
Item
Symbol Value
Unit
Item
Symbol Value
Unit
Rated cooling capacity
P
rated,c
55.0
kW
Seasonal space cooling energy
efficiency
η
s,c
168
%
T
j
= + 35
℃
P
dc
55.0
kW
T
j
= + 35
℃
EER
d
2.44
--
T
j
= + 30
℃
P
dc
43.35
kW
T
j
= + 30
℃
EER
d
3.62
--
T
j
= + 25
℃
P
dc
27.78
kW
T
j
= + 25
℃
EER
d
5.25
--
T
j
= + 20
℃
P
dc
14.81
kW
T
j
= + 20
℃
EER
d
6.51
--
Degradation co-efficient for chillers
(*)
C
dc
0.9
--
Off mode
P
OFF
0.075
kW
Crankcase heater mode
P
CK
0.075
kW
Thermostat-off mode
P
TO
0.6
kW
Standby mode
P
SB
0.075
kW
Capacity control
For air-to-water comfort chillers:
air flow rate, outdoor measured
_
24000
m
3
/h
Sound power level, indoors /
outdoors
L
WA
-/87
dB
Emissions of nitrogen oxides (if
applicable)
NO
x
(**)
--
mg/kWh
input GCV
GWP of the refrigerant
_
2088
kg CO
2 eq
(100 years)
Indoor side heat exchanger chiller:
Water
Information requirements for comfort chillers
Model(s):
CSAD UiAWP 200 PS
Outdoor side heat exchanger of chiller:
Air to water
(*) If C
dc
is not determined by measurement then the default degradation coefficient of chillers shall be 0,9.
(**) From 26 September 2018.
Type:
Compressor driven vapour compression
Driver of compressor:
Electric motor
Declared cooling capacity for part load at given outdoor
temperature T
j
Declared energy efficiency ratio for part load at given outdoor
temperature T
j
Standard rating conditions used:
Low temperature application
(*) If C
dc
is not determined by measurement then the default degradation coefficient of chillers shall be 0,9.
(**) From 26 September 2018.
Power consumption in modes other than 'active mode'
Other items
variable
For water / brine-to-water
chillers: Rated brine or water flow
rate, outdoor side heat
exchanger
_
--
m
3
/h
49
Installation Manual___________________________________________________________________________________