Table 6-1
6.2 Requirements of installation space of
the unit
a. To ensure adequate air flow entering the condenser, the influence
of descending air flow caused by the high-rise buildings around
upon the unit should be taken into account when installing the unit.
b. If the unit is installed where the flowing speed of air is high, such
as on the exposed roof, the measures including sunk fence and
Persian blinds can be taken, to prevent the turbulent flow from
disturbing the air entering the unit. If the unit needs to be provided
with sunk fence, the height of the latter should not be more than that
of the former; if Persian blinds are required, the total loss of static
pressure should be less than the static pressure outside the fan.
The space between the unit and sunk fence or Persian blinds
should also meet the requirement of the minimum installation space
of the unit.
c. If the unit needs to operate in winter, and the installation site may
be covered by snow, the unit should be located higher than the
snow surface, to ensure that air flows through the coils smoothly.
d. To avoid back flow of the air in the codenser and operational
faults of the unit ,the parallel installation of multiple Modular units
can follow the direction and distance as shown in Fig. 6-4, Fig. 6-5
and Table 6-2.
NOTE
After installing the spring damper, the total height of the unit will
increase by 135mm or so.
A
B
C
D
E
F
Model
CSAD UiAWP 200 PS
2220
1325
1055
234
210
470
CSAD UiAWP 100 PS
1870
1000
1175
204
200
470
CSAD UiAWP 300 PS
3220
1513
1095
286
210
470
(unit: mm)
C
Top view
F
D
E
F
D
E
Front view
Left view
Top view
B
C
6.1.3
CSAD UiAWP 300 PS
Front view
Fig. 6-2 Outline dimensional of
CSAD UiAWP 200 PS
Fig. 6-3 Outline dimensional of
CSAD UiAWP 300 PS
A
5
Installation Manual___________________________________________________________________________________