Electrical Heater Operation
a)
After unit is turned on, EH relay will be ON when EH signal is power on and EC motor RPM>300.
b)
If EC motor failure or EC motor RPM is lower than 300RPM, EH relay is opened at once.
Low Temperature Protection of Indoor Coil in Winter
This is frost protection for when the unit is off to prevent water in the coil and room from freezing.
Unit is in Standby Mode
If Ti1
≦
2 ºC for 2 minutes, report error code and Buzzer is beeping for 3 minutes.