Page
53
of 61
SK2019 FCSD 1V-01-EC-001_1
LED Display and Error Description
Flexible Control PCB -
FLEXI
Control Type
Fan speed setting
LED Display
Condition
High speed
Red LED On
Normal
Medium speed
Yellow LED On
Normal
Low speed
Green LED On
Normal
For all units - Green LED blinks
Item
Blink
Reason
Remedy
Indoor coil sensor 1 failure
Green LED blinks 4 times,
stops for 3s
Ti1 sensor connection is
damaged.
1.
Check if Ti1 plug is
connected or not.
2.
Check sensor’s resistor is
good or not.
Water pump failure
Green LED blinks 7 times,
stops for 3s
Float switch is opened.
1.
Check if the condensate
water pipe is connected or
not.
2.
Check if the pump is
functioning or not.
EC motor failure
Green LED blinks 9 times,
stops for 3s
No EC motor feedback
1.
Check DIPB-SW5 and SW6
setting.
2.
Check the EC motor
Anti-frozen protection
Green LED blinks 11 times,
stops for 3s
When unit is standby,
Ti1<2ºC.
Turn on unit to keep Ti higher
than 5ºC.